2022-08-15 13:51:50 | RESIDENTIAL (R3) ALTERATION SEVENTH BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #:19100548 416 42ND ST # A |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 505 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| ADDITIONS SEC. 507 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| A)FORM R405-2020 SUBMITTED IS THE WRONG FORM. THIS |
| PROJECT IS REVIEWED UNDER THE 2017 CODE. PROVIDE |
| CORRECT FORM R405-2017 AS DONE ON PREVIOUS SUBMITTAL. |
| |
| B) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR |
| OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER |
| SHALL CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF |
| FORM THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, |
| AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R101.5.1.1.2 |
| FBC-RESIDENTIAL. |
| |
| C)CONDITIONED FLOOR AREA ON PAGE ONE DOESN'T MATCH AREA |
| SHOWN ON PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| NOTE: IT IS NOT CLEAR IF THE ENERGY CALCULATIONS ARE |
| DONE FOR ENTIRE FIRST FLOOR OR JUST THE REBUILT FIRST |
| FLOOR BEDROOM. REVISE AS REQUIRED. |
| ENERGY CALCULATIONS MAY DONE JUST FOR THE NEW |
| CONSTRUCTION OF THE BEDROOM AS SHOWN ON PLANS TO AVOID |
| MORE CONFLICTS/DELAYS. |
| |
| D)REVISE WALL TYPE INFORMATION ON PAGE ONE. COORDINATE |
| WITH ITEM #1(B) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) REVISE BLOCKS, SPACES, FLOORS, ROOF AND ATTIC |
| INFORMATION ON PAGE 2. COORDINATE WITH ITEM #1(B) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE CEILING, WALL, DOORS, WINDOWS AND HEATING |
| SYSTEM INFORMATION ON PAGE 3. COORDINATE WITH ITEM |
| #1(B) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC- |
| ENERGY CONSERVATION. |
| |
| 2- OK. |
| |
| |
| NOTE: |
| ARCHITECTURAL PLANS SUBMITTED ARE OLD PLANS. THEY WERE |
| SIGNED AND SEALED BY THE ARCHITECT OF RECORD ON |
| 7/21/20. THE FOLLOWING COMMENTS ARE BASED ON THESE OLD |
| PLANS. |
| |
| |
| 3- SHEET 1.1: NEED TO SPECIFY MIN. 5/8" ROOF SHEATHING |
| AS REQUIRED BY SEC. TABLE R803.1 FBC-RESIDENTIAL. |
| NOTE: THIS COMMENT APPLIES TO TYPICAL WOOD FRAME WALL |
| SECTION ON SHEET 3.1 ALSO. |
| |
| 4- OK |
| |
| 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1 |
| ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2) |
| FBC-RESIDENTIAL AND HEIGHT AND EXPOSURE ADJUSTMENT |
| TABLE R301.2(3) FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA |
| AS REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR |
| PROVIDE CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED |
| ON THE LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT |
| AND BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 6- SHEET 3.1: NEED TO SPECIFY TOP AND THE BOTTOM |
| CONNECTORS AT THE STRUCTURAL FRAME MEMBERS OF THE |
| SECTION AT WOOD FRAME IN-FILL DETAIL. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 7- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)OUTSWING ENTRY DOOR AND ENLARGED BEDROOM EXTERIOR |
| DOOR AS SHOWN ON PLANS. |
| DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT |
| APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS |
| THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO |
| COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5 |
| ABOVE. |
| |
| B)HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT APPROVALS |
| DON'T HAVE IMPACT GLAZING. |
| NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| SAMPLE. |
| |
| C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (NOTE: |
| INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY |
| SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS |
| TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. DESIGNER |
| OF RECORD NEEDS TO PROVIDE THE DETAILS AND |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE STAIRS. |
| ALSO, DESIGNER OF RECORD NEEDS TO PROVIDE THE DETAILS |
| AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| HANDRAILS AND GUARDRAILS AS REQUIRED BY TABLE R301.5, |
| SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL. |
| NOTE: SUBSEQUENT HANDRAIL/GUARDRAIL SHOP DRAWINGS ARE |
| TO CONFIRM THAT DESIGN DETAILS AND SPECIFICATIONS ARE |
| MET. |
| |
| 10- ORIGINAL STAIRWAY WAS LOCATED IN THE MIDDLE OF THE |
| BUILDING. NEW STAIRWAY IS LOCATED ON THE EXTERIOR SIDE |
| OF THE BUILDING. ARCHITECT OF RECORD NEEDS TO SHOW HOW |
| THE SECOND FLOOR WAS AFFECTED TO ALLOW THE NEW |
| STAIRWAY. SHOW ALL REQUIRED CONSTRUCTION TO ALLOW NEW |
| STAIRWAY TO SERVE THE SECOND FLOOR ENTRY TO THE |
| APARTMENT. SHOW ALL EXTERIOR CONSTRUCTION SHOWN ON THE |
| WEST ELEVATION. ON SHEET 2.1. SEC. 107.2.1 CITY |
| AMENDMENTS. THIS WAS REMOVED TO ALLOW FOR FIRST FLOOR |
| BEDROOM RECONSTRUCTION. |
| |
| 11- ROOF FRAMING PLAN AND TYPICAL WALL SECTION DON'T |
| SPECIFY THE CONNECTION OF THE 2X12 ROOF JOIST. SPECIFY |
| CONNECTOR. SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 12- TYPICAL WALL SECTION ON SHEET 3.1: |
| A) SPECIFY CEILING INSULATION. SEC. R103.2.1 FBC-ENERGY |
| CONSERVATION. |
| |
| B)SPECIFIED VENT 6"X26" SCREEN VENT AT 6'-0" DOESN'T |
| PROVIDE CROSS VENTILATION. THIS IS A FLAT ROOF. REVISE |
| AS REQUIRED. SEC. R806 FBC-RESIDENTIAL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |