Plan Review Notes For Permit 19100548 |
Permit Number |
19100548 |
|
Review Stop |
R |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2022-08-15 13:52:49 | ROOFING REVIEW: | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR: | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | ************************ | | | | |
|