2021-03-12 12:05:42 | RESIDENTIAL (R3) ADDITION/ALTERATION, FIFTH BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT # 19100548 |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| ENERGY CALCULATIONS SUBMITTED: |
| |
| REPEAT COMMENT. |
| A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| BEGIN CONSTRUCTION. |
| |
| REPEAT COMMENT. |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- |
| ENERGY CONSERVATION. |
| |
| REPEAT COMMENT. |
| C) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS |
| INCORRECT. IT DOESN'T MATCH PLANS. SEE PLANS AND REVISE |
| AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| REPEAT COMMENT. |
| D) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 |
| TO MATCH PLANS. THIS IS FOR ENTIRE FIRST FLOOR. SEE |
| PLANS/ELEVATIONS AND REVISE AS REQUIRED. CHECK WINDOWS |
| OVERHANG AND SEPARATION ALSO. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 3 OF 4 |
| DOESN'T MATCH PLANS/ELEVATIONS. PLANS SHOW FLAT ROOF NO |
| HIP. SEE PLANS AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC- |
| ENERGY CONSERVATION. |
| |
| 2- OK. |
| 3- OK |
| 4- OK. |
| |
| ORIGINAL COMMENT: |
| 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1 |
| ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2) |
| FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE |
| R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE |
| THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS |
| REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE |
| CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE |
| LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT AND |
| BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE |
| TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS |
| BUILDING IS IN EXPOSURE "C". NEED TO MULTIPLE PRESSURES |
| BY COEFFICIENT SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL |
| BASED ON THE HEIGHT OF THE BUILDING. REVISE AS |
| REQUIRED. NOTE: THIS IS A TWO STORY BUILDING. |
| |
| 6- OK |
| |
| ORIGINAL COMMENT. |
| 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL) |
| |
| A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT |
| APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS |
| THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO |
| COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5 |
| ABOVE. |
| |
| B)SINGLE HUNG WINDOWS. OK |
| |
| C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT |
| APPROVALS DON'T HAVE IMPACT GLAZING. |
| PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING |
| |
| RESPONSE: |
| SWING DOOR PRODUCT APPROVAL SUBMITTED DON'T HAVE IMPACT |
| GLAZING. COORDINATE WITH ITEM # 7.A) ABOVE. |
| |
| NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| SAMPLE |
| |
| D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. CONTRACTOR DIDN'T |
| EVEN SPECIFIED IF SUBMITTING LATER AS A DEFERRED |
| SUBMITTAL. |
| |
| 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS |
| TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THIS STAIRWAY |
| OR CLARIFY IF SUBMITTING THIS INFORMATION UNDER A |
| SEPARATE PERMIT. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 10- ALL DRAWINGS SUBMITTED ARE NOT SIGNED AND SEALED BY |
| THE ARCHITECT OF RECORD. ARCHITECT TO SIGN AND SEAL |
| DRAWING AS REQUIRED BY 61G1-16.001FAC AND CHAPTER 481 |
| F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC |
| RECORDS. |
| |
| NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE |
| OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL |
| AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL |
| FOR RECORDS RETENTION. |
| |
| 11- ARCHITECT TO REVISE TYPICALLY WALL SECTION ON SHEET |
| 3.1. |
| SCREEN VENTS SPACED AT 6'-0" O.C. DON'T PROVIDE CROSS |
| VENTILATION AS REQUIRED BY SEC. R806 FBC-RESIDENTIAL. |
| THIS IS A FLAT ROOF WITH SOLID 2X12 ROOF JOISTS. |
| TYPICALLY, A CONTINUOUS VENT IS INSTALLED IN THIS TYPE |
| OF ROOFS. REVISE AS REQUIRED. SPECIFY VENT TYPE AND |
| SIZE THAT WILL PROVIDE REQUIRED CROSS VENTILATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |