2019-12-10 10:47:23 | RESIDENTIAL (R3) ALTERATION LEVEL 3, SECOND BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT # 19100548 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ****IMPORTANT***** |
| ENERGY CALCULATIONS NEED TO BE SIGNED/DATED BY THE |
| OWNER PRIOR TO PASSING THE BUILDING REVIEW WITH |
| PROVISO. |
| |
| |
| |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| ENERGY CALCULATIONS SUBMITTED: |
| A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| BEGIN CONSTRUCTION. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- |
| ENERGY CONSERVATION. |
| |
| C) ITEM #1 ON PAGE 1 OF 4 IS INCORRECT. THIS IS NOT NEW |
| CONSTRUCTION. THIS IS EXISTING BUILDING. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| D) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS |
| INCORRECT. REVISE AS REQUIRED. CLARIFY WHY THE AREAS |
| DON'T MATCH AREAS SHOWN ON THE PROPERTY APPRAISER |
| WEBSITE IF THE FOOTPRINT SEEMS TO BE THE SAME. SEC. |
| R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| E) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 |
| TO MATCH PLANS. REVISE OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 2- OK. |
| |
| 3- OK |
| |
| 4- OK. |
| |
| 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1 |
| ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2) |
| FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE |
| R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE |
| THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS |
| REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE |
| CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE |
| LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHTT AND |
| BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE |
| TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS TABLE |
| IS BASED ON BUILDING EXPOSURE "B". THIS BUILDING IS IN |
| EXPOSURE "C". NEED TO MULTIPLE PRESSURES BY COEFFICIENT |
| SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL BASED ON THE |
| HEIGH OF THE BUILDING.. REVISE AS REQUIRED. NOTE: THIS |
| IS A TWO STORY BUILDING. |
| |
| 6- OK |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL) |
| |
| |
| A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| NOTE: NOA 16-0617.02 SUBMITTED IS FOR SLIDING GLASS |
| DOORS. THERE ARE NOT SLIDING GLASS DOORS ON THIS |
| PROJECT. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T |
| SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL. |
| |
| B)SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T |
| SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL. |
| |
| C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT |
| APPROVALS DON'T HAVE IMPACT GLAZING. |
| PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 |
| FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T |
| SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL. |
| |
| NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE |
| INSTALLATION SCHEDULE AS REQUIRED BY CITY |
| IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY |
| SAMPLE |
| |
| NEW COMMENT BASED ON REVISED PLANS. |
| D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY |
| SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |