Plan Review Notes For Permit 19100519 |
Permit Number |
19100519 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-06-01 16:04:58 | | | 2ND REVIEW FBC-2017 FUEL GAS | | PERMIT- 19100519 | | 6/1/2020 | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENTS FROM THE 1ST REVIEW WERE NOT ADDRESSED- SEE | | BELOW. | | | | 1) COMBUSTION AIR CALCULATIONS REQUIRED- SECTION 304.1 | | FBC FG. INDICATE HOW THE AIR IS TO BE PROVIDED- | | INDOORS, OUTDOORS, OR MECHANICALLY. | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES | | INCLUDING THE WATER HEATERS- SECTIONS 305.1 & 624.1 FBC | | FG. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|