Plan Review Notes For Permit 19100519 |
Permit Number |
19100519 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-06-01 13:33:17 | REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWING 308LS SHOWS BUILDING CONSTRUCTION TYPE AS | | (IB) - DRAWING G0.01 SHOWS BUILDING CONSTRUCTION TYPE | | AS (IIIA) - PLEASE CLARIFY. | | 2) STRUCTURAL CALCULATIONS AND DRAWING (S1.0) SHOWS | | DESIGN WIND SPEED AS 169MPH - SHOULD BE 170MPH PER FBC | | WPB AMENDMENTS 120.1 | | 3) STRUCTURAL CALCULATIONS FOR THE DUMPSTER - DESIGN | | WIND SPEED USED IS 115MPH - SHOULD BE MIN. 150MPH PER | | FBC WPB AMENDMENTS 120.1 | | | | |
|