Date |
Text |
2019-12-17 11:39:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET 319A - THERE IS AN INDICATION OF DRY STORAGE |
| UNDER THE SOUTH STAIR. THGERE IS NO STAIR DETAIL |
| INDICATING THE REQUIRED SEPARATION OF THE STARIWELL. |
| |
| PER NFPA 101. |
| |
| 7.2.2 STAIRS. |
| 7.2.2.1 GENERAL. |
| 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF |
| EGRESS SHALL |
| CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| TO THE |
| SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE |
| SPECIFIED IN |
| 7.2.2.1.2. |
| |
| 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| 7.2.2.5.1 ENCLOSURES. |
| 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| EXIT COMPONENT |
| SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| |
| 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN |
| EXIT |
| ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER STAIRS, |
| UNLESS |
| OTHERWISE PERMITTED BY 7.2.2.5.3.2. |
| |
| 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED |
| UNDER STAIRS, |
| PROVIDED THAT BOTH ALL OF THE FOLLOWING CRITERIA ARE |
| MET: |
| (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| ENCLOSURE BY THE |
| SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE. |
| (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| FROM |
| WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) |
| (3) THE SPACE IS NOT USED FOR THE STORAGE OF |
| COMBUSTIBLE OR |
| FLAMMABLE LIQUIDS, OR OTHERWISE HAZARDOUS MATERIALS. |
| |
| PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| CONSTRUCTION. |
| |
| |
| 2) SHEET 319 A - THE NORTH STAIR DOES NOT INDICATE THE |
| REQUIRED SEPARATION DETAIL AS NOTED IN # 1 ABOVE. |
| |
| PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| CONSTRUCTION. |
| |
| |
| |
| 3) SHEET 319 A - THE IS A STAGE INDICATED. |
| |
| THERE ARE NO INDICATION OF THE CONSTRUCTION FEATURES OF |
| THE STAGE. |
| |
| PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| CONSTRUCTION. |
| |
| |
| |
| 4) SHEET 320 A - THERE ARE NO INDICATIONS OF DOOR |
| HARDWARE WITHIN THE DOOR SCHEDULE. |
| |
| PLEASE REVIEW AND PROVIDE PER THE APPLICABLE OCCUPANCY |
| CODE. |
| |
| |
| 5) SHEET 308 A - THERE IS AN INDICATION OF AN ASSEMBLY |
| OCCUPNACY; HOWEVER, THERE ARE TWO RESIDENTIAL |
| OCCUPANCIES. |
| |
| IS THIS A MIXED OR SEPARATED OCCUPANCY? |
| |
| PLEASE PROVIDE PER NFPA 101 CH 6, OCCUPANCY |
| CLASSIFICATION. |
| |
| 6.1.14.2 DEFINITIONS. |
| 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| IN WHICH TWO |
| OR MORE CLASSES OF OCCUPANCY EXIST. |
| 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| THE |
| OCCUPANCIES ARE INTERMINGLED. |
| 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| WHERE THE |
| OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| ASSEMBLIES. |
| 6.1.14.3 MIXED OCCUPANCIES. |
| 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| CLASSIFIED AS TO ITS USE IN |
| ACCORDANCE WITH SECTION 6.1. |
| 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| RESTRICTIVE |
| REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| SEPARATE SAFEGUARDS |
| ARE APPROVED. |
| 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| EACH PART OF THE |
| BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| IN THIS CHAPTER, |
| SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| FIRE-RESISTIVE |
| ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| TABLE 6.1.14.4.1(A), |
| AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| BY APPROVED |
| EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| 6.1.14.4.6. |
| |
| 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| HORIZONTAL, OR |
| BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| TO PROVIDE |
| COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| BUILDING. |
| 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| SHALL COMPLY |
| WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| |
| PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF |
| CONSTRUCTION. |
| |
| |
| 6) SHEET 336 A - THE THREE MAIN EXIT DOORS TO THE |
| ASSEMBLY AREA SHOW HARDWARE SET # 6. RIM CYLINDER, |
| MORTISE DEVICE AND FLOOR STOP. |
| |
| THESE MAY NOT BE COMPLIANT WITH THE REQUIRED EXIT |
| HARDWARE, PER NFPA 101, CH 12 & CH 7. |
| |
| 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| AN AREA HAVING |
| AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| PERMITTED TO BE |
| PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| IS PANIC |
| HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| UNLESS |
| OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| |
| (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| LOCKS AS |
| PERMITTED IN 12.2.2.2.5. |
| (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| ACCESS-CONTROLLED EGRESS DOORS |
| AS PERMITTED IN 12.2.2.2.6. |
| 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| SHALL BE PERMITTED |
| TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| IF BOTH OF THE |
| FOLLOWING CONDITIONS APPLY: |
| (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| AND THE ASSEMBLY |
| OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| ASSEMBLY |
| OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| RELEASED |
| BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| |
| 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM |
| THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| TO DOOR |
| LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| ELEVATED |
| TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| LABORATORY |
| FIRE TEST PROCEDURES. |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A |
| TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| THE EGRESS |
| SIDE. |
| 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| SHALL NOT |
| APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| 23. |
| |
| 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| EQUIPPED WITH |
| PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| ALL OF THE |
| FOLLOWING CRITERIA: |
| (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| ACTUATING |
| PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| OF THE |
| WIDTH OF THE DOOR LEAF. |
| (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| (865 MM), |
| AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| IN. (760 MM), |
| AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| NOT TO EXCEED |
| 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| LATCHES. |
| |
| PLEASE REVIEW AND CORRECT OF PROVIDE CODE COMPLIANT |
| JUSTIFICATION. |
| |
| |
| 7) SHEET 319 A - THERE IS AN INDICATION OF A STAGE AND |
| BAR IN THIS ASSEMBLY OCCUPANCY AND COULD BE CONSIDERED |
| A NIGHCLUB |
| |
| PER NFPA 101, CH 12 |
| |
| 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE |
| FOLLOWING |
| ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY |
| AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 9.7.1.1(1): |
| (1) DANCE HALLS |
| (2) DISCOTHEQUES |
| (3) NIGHTCLUBS |
| (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| |
| PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION OF JUSTIFY |
| WITH DETAILED NARRATIVE AND CODE REFERNCES. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| |