2019-10-30 15:59:04FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) NOTE: THIS IS NOT A DESIGNATED SIGN ZONE LOCATION IN
 THE CITYPLACE MASTER SIGN PLAN. CITYPLACE RETAIL HAS
 SUBMITTED A MINOR PLANNED DEVELOPMENT AMENDMENT FOR THE
 RELOCATION OF THE SIGN OUTSIDE OF THE SIGN ZONE.
  
 2) THE CITYPLACE MASTER SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE
 AN ELEVATION DRAWING SHOWING THE LINEAR FEET OF STORE
 FRONTAGE BEING USED FOR THIS SIGN.
  
 PERMITTED SIGNAGE: ?
 PROPOSED SIGN: 21.875 SF
  
 3) THE HALO LIT CHANNEL LETTER SECTION LISTS THE LETTER
 DEPTH AS 3 INCHES; HOWEVER, THE FULL SIGN SECTION
 DRAWING SHOWS THE LETTER DEPTH AS 2.5 INCHES. ALL
 DRAWINGS MUST SHOW THE SAME CONDITIONS.
  
 4) HOW DOES THE WIRE RUN FROM THE SIGN BOARDER TO THE
 INDIVIDUAL LETTERS? THE SIGN ELEVATION DRAWING SHOWS
 THEM IN A HORIZONTAL PLAIN IN LINE WITH THE
 PERFORATIONS. HOW WILL THIS WIRE KEEP FROM BEING
 EXPOSED THROUGH THE HOLES, WHETHER IT IS IN A LINE OR
 IF THE WIRE SAGS?
  
 5) HOW IS THE LED STRIP FASTENED TO THE ALUMINUM SIGN
 BORDER? THE SECTION VIEW SHOWS DOES NOT SHOW IT
 CONNECTED TO ANYTHING.
  