Plan Review Notes For Permit 19100442 |
Permit Number |
19100442 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-21 16:12:34 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | 1. FBC B 107.2.1 & CITY OF WPB AMENDMENT 107.2.1.1, | | PROVIDE REVIEW STAMPED AND SIGNED PRODUCT APPROVALS FOR | | ROOFING MATERIALS INCLUDING UNDERLAYMENT, TILE, & TILE | | ADHESIVE. | | 2. FBC R 703.7.3 PROVIDE A CLARIFICATION ON STUCCO | | NOTES THAT WILL INCLUDE A WATER RESISTIVE VAPOR BARRIER | | IN ADDITION TO THE PAPER BACKED LATH. | | | | NOTES: | | | | 1. A SEPERATE ROOF PERMIT WILL BE REQUIRED PRIOR TO | | ROOF WORK. | | 2. TRUSS ENGINEERING SIGNED AND SEALED BY TRUSS | | ENGINEER WILL BE REQUIRED FOR FIELD INSPECTOR. | | 3. THE ENTRY GATE SHOP DRAWINGS REVIEW STAMPED AND | | SIGNED BY DESIGNER OF RECORD ARE REQUIRED FOR FIELD | | INSPECTOR. | | |
|