Plan Review Notes
Plan Review Notes For Permit 19100434
Permit Number 19100434
Review Stop G
Sequence Number 1
Notes
Date Text
2019-10-22 04:55:161) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 STATES" REMODEL MASTER BATH" YET GAS PLANS HAVE BEEN
 SUBMITTED. CLARIFY. REVISE THE DESCRIPTION OF WORK ON
 THE PERMIT APPLICATION.
 2) THE GAS PLAN NOTES A 2 PSI SYSTEM BUT THE TABLES
 REFERENCED ON THE GAS DRAWING ARE FOR LESS THAN A 2 PSI
 SYSTEM. CLARIFY.
 3) THE PERMIT APPLICATION NOTES THE JOB ADDRESS AS 233
 RILYN DR. BUT THE GAS PLAN HAS THE ADDRESS AS 235 RILYN
 DR. CLARIFY.
 4) IF THIS IS A 2 PSI SYSTEM, SHOW THE LOCATION OF ALL
 REGULATORS AND SHOW THE DISTANCE FROM EACH REGULATOR TO
 THE FURTHEST OUTLET ON THAT BRANCH LINE.
 5) CLEARLY SHOW ALL PIPE SIZES ON THE GAS DRAWING, SOME
 OF THE SIZES ARE DIFFICULT TO READ. WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 STOVE, THE DRYER, AND FOR THE TANKLESS WATER HEATER IF
 IT IS NOT LOCATED ON THE EXTERIOR OF THE BUILDING PER
 THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES
 DRYERS) OR 2017 FBC-RES. SEC.G 2407.1 AND G2439.4
 (CLOTHES DRYERS).
 7) SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 8) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE
 LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 10) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL
 GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.
 11) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC. 410.2 (7).
 12) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF ALL OF THE GAS APPLICANCES.
 13) A YELLOW INSULATED COPPER TRACER WIRE OR OTHER
 APPROVED CONDUCTOR SHALL BE INSTALLED ADJACENT TO
 UNDERGROUND NONMETALLIC PIPING. THE WIRE SHALL NOT BE
 IN CONTACT WITH HE NONMETALLIC PIPE. 2017 FBC-FUEL GAS
 SEC.404.17.3.
  
 ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
 ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
  
  