Plan Review Notes For Permit 19100294 |
Permit Number |
19100294 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-08 07:25:32 | 10/08/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON | | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE | | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | 2. SUBMIT MANUFACTURER?S SPECIFICATION | | SHEETS/INSTALLATION MANUAL FOR GENERATOR TO VERIFY | | COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. | | 3. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF | | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. | | 4. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 | | FBC RES. SEC. G2419.2. 55. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|