Plan Review Notes For Permit 19100232 |
Permit Number |
19100232 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-28 16:42:22 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION IS DENIED BY BUILDING. | | THE REVISION TO PERMIT NUMBER 17110857 IS DENIED. | | PLEASE ADDRESS THE FOLLOWING COMMENTS. | | | | 1) REMOVING THE LOWER TERRACE AREA FROM THE NORTH SIDE | | OF THE BUILDING WILL ELIMINATE THE NORTHEAST EMERGENCY | | EXIT UNTIL THE TERRACE HAS BEEN COMPLETED. SUBMIT A | | REVISED FIRST FLOOR LIFE SAFETY PLAN. FBC 107.2.1 | | | | 2) SPECIFY HOW FALL PROTECTION WILL BE PROVIDED AT THE | | LANDING AND STAIRS THAT ARE ADJACENT TO THE LOWER | | TERRACE AREA. FBC 1015 | | | | 3) A SEPARATE PERMIT APPLICATION, PLANS AND REVIEWS | | WILL BE REQUIRED FOR THE FIRST FLOOR TERRACE AND ENTRY | | CHANGES. FBC 105 AND 107 | | | | 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. |
|