Plan Review Notes For Permit 19100169 |
Permit Number |
19100169 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-02-03 15:07:11 | 02/03/20 3RD PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THRID REQUEST PLEASE SUBMIT A SANITARY RISER DIAGRAM | | FOR ALL CHANGES BEING MADE TO THE PLUMBING SYSTEM PER | | THE WPB AMEND. TO FBC SEC. 107.3.5.3. | | 2. THIRD REQUEST, THE WASHING MACHINE STANDPIPE SHALL | | CONNECT TO A 3 INCH OR LARGER DIAMETER FIXTURE BRANCH | | OR STACK PER THE 2017 FBC-PLUMBING SEC.406.2 AND | | MANUFACTURES SPECIFICATION. | | 3. THE SHUT OFF VALVES FOR STACKABLE WASHING MACHINE | | SHALL BE ACCESSIBLE WITHOUT MOVING MACHINE PER THE 2017 | | FBC PL 606.3. | | | | NEW COMMENT: A PLUMBER MAY SUBMIT AN ISOMETRIC DRAWING | | FOR COMMENT ONE AND ADDRESS COMMENT TWO IN THE DRAWING. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|