Plan Review Notes
Plan Review Notes For Permit 19100169
Permit Number 19100169
Review Stop P
Sequence Number 3
Notes
Date Text
2020-02-03 15:07:1102/03/20 3RD PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THRID REQUEST PLEASE SUBMIT A SANITARY RISER DIAGRAM
 FOR ALL CHANGES BEING MADE TO THE PLUMBING SYSTEM PER
 THE WPB AMEND. TO FBC SEC. 107.3.5.3.
 2. THIRD REQUEST, THE WASHING MACHINE STANDPIPE SHALL
 CONNECT TO A 3 INCH OR LARGER DIAMETER FIXTURE BRANCH
 OR STACK PER THE 2017 FBC-PLUMBING SEC.406.2 AND
 MANUFACTURES SPECIFICATION.
 3. THE SHUT OFF VALVES FOR STACKABLE WASHING MACHINE
 SHALL BE ACCESSIBLE WITHOUT MOVING MACHINE PER THE 2017
 FBC PL 606.3.
  
 NEW COMMENT: A PLUMBER MAY SUBMIT AN ISOMETRIC DRAWING
 FOR COMMENT ONE AND ADDRESS COMMENT TWO IN THE DRAWING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  