 PREVIOUS COMMENTS HAVE NOT BEEN COMPLIED WITH.
 1) SUBMIT A SANITARY RISER DIAGRAM FOR ALL CHANGES
 BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 2) THE WASHING MACHINE STANDPIPE SHALL CONNECT TO A 3
 INCH OR LARGER DIAMETER FIXTURE BRANCH OR STACK.
 FBC-PLUMBING SEC.406.2.
  
 NEW COMMENT:
 1. THE SHUT OFF VALVES FOR STACKABLE WASHING MACHINE
 SHALL BE ACCESSIBLE WITHOUT MOVING MACHINE. PER FBC PL
 606.3
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH