2020-01-02 13:41:54 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19100169 |
| 1/2/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE AN AHRI CERTIFICATE FOR THE NEW 5-TON AC |
| SYSTEM- SECTION R501.7 FBC EC. |
| |
| 2) THE RESUBMITTED PLAN SHOWS THE AIR HANDLER IN THE |
| ATTIC. PLEASE SHOW COMPLIANCE WITH SECTION M1305.1.3 |
| FBC RES, & SECTION R403.3.6 FBC EC. |
| |
| M1305.1.3 APPLIANCES IN ATTICS. |
| |
| ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN |
| OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE |
| ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT |
| NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG |
| MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30 |
| INCHES (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES |
| OF THE APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR |
| ACCESS OPENING DIMENSIONS SHALL BE NOT LESS THAN OF 20 |
| INCHES BY 30 INCHES (508 MM BY 762 MM), AND LARGE |
| ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. |
| EXCEPTIONS: |
| 1.THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE NOT |
| REQUIRED WHERE THE APPLIANCE CAN BE SERVICED AND |
| REMOVED THROUGH THE REQUIRED OPENING. |
| 2.WHERE THE PASSAGEWAY IS UNOBSTRUCTED AND NOT LESS |
| THAN 6 FEET (1829 MM) HIGH AND 22 INCHES (559 MM) WIDE |
| FOR ITS ENTIRE LENGTH, THE PASSAGEWAY SHALL BE NOT MORE |
| THAN 50 FEET (15 250 MM) LONG. |
| |
| R403.3.6 AIR-HANDLING UNITS. |
| |
| AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| CONDITIONS ARE MET: |
| 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN |
| THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER. |
| 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |