Plan Review Notes
Plan Review Notes For Permit 19100169
Permit Number 19100169
Review Stop M
Sequence Number 2
Notes
Date Text
2020-01-02 13:41:542ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19100169
 1/2/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN AHRI CERTIFICATE FOR THE NEW 5-TON AC
 SYSTEM- SECTION R501.7 FBC EC.
  
 2) THE RESUBMITTED PLAN SHOWS THE AIR HANDLER IN THE
 ATTIC. PLEASE SHOW COMPLIANCE WITH SECTION M1305.1.3
 FBC RES, & SECTION R403.3.6 FBC EC.
  
 M1305.1.3 APPLIANCES IN ATTICS.
  
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES
 OF THE APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR
 ACCESS OPENING DIMENSIONS SHALL BE NOT LESS THAN OF 20
 INCHES BY 30 INCHES (508 MM BY 762 MM), AND LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
 EXCEPTIONS:
 1.THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE NOT
 REQUIRED WHERE THE APPLIANCE CAN BE SERVICED AND
 REMOVED THROUGH THE REQUIRED OPENING.
 2.WHERE THE PASSAGEWAY IS UNOBSTRUCTED AND NOT LESS
 THAN 6 FEET (1829 MM) HIGH AND 22 INCHES (559 MM) WIDE
 FOR ITS ENTIRE LENGTH, THE PASSAGEWAY SHALL BE NOT MORE
 THAN 50 FEET (15 250 MM) LONG.
  
 R403.3.6 AIR-HANDLING UNITS.
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER