Plan Review Notes
Plan Review Notes For Permit 19100169
Permit Number 19100169
Review Stop B
Sequence Number 2
Notes
Date Text
2019-12-20 15:18:02 
 RESIDENTIAL (R3) ALTERATION/ADDITION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 ORIGINAL COMMENT:
 1- GARAGE IS CONVERTED TO ADDITIONAL LIVABLE AREA.
 PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS ARE SIGNED
 BY ALL THE REQUIRED PARTIES AND COORDINATE WITH PLANS
 TO AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY CALCULATIONS SUBMITTED IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM OF THE FORM BY THE OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNED BY THE OWNER PRIOR TO RECEIVE THE PERMIT AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) REVISE ITEM # 1. THIS IS NO NEW CONSTRUCTION. THIS
 IS EXISTING CONSTRUCTION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 E) "SPACES" INFORMATION ON PAGE 3 SPECIFIES THAT THERE
 IS NOT KITCHEN. THIS IS INCORRECT. ACCORDING TO THE
 CONDITIONED FLOOR AREA SPECIFIED (2586 S.F.) THESE
 CALCULATIONS ARE DONE FOR ENTIRE HOUSE. THERE IS A
 KITCHEN IN THIS HOUSE. ALSO, CLARIFY WHY THERE ARE ZERO
 BEDROOMS. REVISE AS REQUIRED TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE THE ATTIC VENT RATIO ON PAGE 3. THE RATIO IS
 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR,
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2.
  
 G) WINDOWS INFORMATION ON PAGE 4 IS INCORRECT. REVISE
 WINDOWS ORIENTATION, AREA AND OVERHANG DEPTH AND
 SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 2- OK
  
 ORIGINAL COMMENT:
 3- PLANS DON'T SPECIFY THE WIND DESIGN CRITERIA AS
 REQUIRED BY SEC. 1101.1 FBC-EXISTING BUILDING AND SEC.
 R301.2.1 FBC-RESIDENTIAL. SPECIFY THE ULTIMATE AND
 NOMINAL WIND LOADS, BUILDING EXPOSURE AND PROVIDE THE
 DESIGN PRESSURES FOR ALL DOORS AND WINDOWS.
 NOTE: THIS HOUSE IS LOCATED IN EXPOSURE "D". SEC.
 R301.2.1.4.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISE COMPONENTS AND CLADDING DESIGN PRESSURES
 PROVIDED UNDER THE DESIGN CRITERIA. ARCHITECT SPECIFIES
 THAT THE DESIGN PRESSURES PROVIDED ARE FOR THE WORST
 CASE SCENARIO.
 DESIGN PRESSURES PROVIDED ARE TOO LOW. REVISE AS
 REQUIRED. WORST CASE SCENARIO WOULD BE AN EFFECTIVE
 AREA OF 10S.F. IN ZONE 5 FOR WALLS AND 10S.F IN ZONE 3
 FOR ROOFS. REVISE AS REQUIRED. OR PROVIDE THE DESIGN
 PRESSURES FOR THE ACTUAL WALL OPENING SIZE AND
 LOCATION.
 TABLE R301.2(2) FBC-RESIDENTIAL WITH APPLICABLE
 ADJUSTMENTS FROM TABLE R301.2(3) FBC-RESIDENTIAL
  
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 1101.1 FBC-EXISTING BUILDING AND FAC 61G20-3.001
 FOR:
  
 A) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 NOA 12-0612.16 EXPIRED ON AUGUST 03,2016. AND IS
 MISSING THE INSTALLATION DRAWINGS.
 NOTE: THIS NEEDS TO BE COORDINATED WITH THE BUILDING
 OFFICIAL (OUT OF OFFICE TODAY)
  
 B) OK
  
 C) OK
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 THIS IS TO BE COORDINATED WITH SLIDING GLASS DOORS
 APPROVAL.
  
  
 6- OK
  
 7- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 8- FOR INFORMATION ONLY: THIS BUILDING IS LOCATED IN
 FLOOD ZONE AE WITH THE BASE FLOOD BFE: 7 FEET BASED ON
 NAVD 1988. AFTER MEETING WITH ROBERT BROWN AND OWNERS
 (JOHNSON JEREMY AND JOHNSON RITA) IT WAS DETERMINED
 THAT WORK WAS DONE BY PREVIOUS OWNER WITHOUT PERMITS.
 CURRENT OWNER PURCHASED THE HOUSE ON APRIL 2012.
 THEREFORE, THIS WORK DOESN'T COUNT FOR THE FIVE YEAR
 PERIOD TO BE CONSIDERED BY CITY ORDINANCE TO DETERMINE
 IF THIS WORK WOULD BE CONSIDERED "SUBSTANTIAL
 IMPROVEMENT". FUTURE WORK WILL BE CONSIDERED TO
 DETERMINE IF THE SUBSTANTIAL IMPROVEMENT THRESHOLD IS
 MET.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  