2019-10-08 14:36:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE WAS NO SITE PLAN PROVIDED SHOWING LOCATION OF
 THE PROPOSED TENT INCLUDING DIMENSIONS TO NEAREST
 BUILDING, OTHER TENTS AND PARKING AREAS.
  
 PLEASE PROVIDE.
  
  
  
 2) THERE ARE NO INDICATIONS IF THE TENT(S) HAS SIDES
 FOR FREE EGRESS OR SIDES WITH PROPOSED EXIT LOCATION.
  
 PLEASE PROVIDE.
  
  
  
 3) THERE ARE NO INDICATIONS OF HOW THE TENTS WILL BE
 HELD DOWN.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO INDICATIONS OF HOW LONG THE TENTS WILL
 BE UP AND REMAIN ON SITE.
  
  
 PLEASE PROVIDE DATES AND TIMES.
  
  
  
 5) THERE ARE NO INDICATIONS OF ANY PROPOSED
 FLOOR/SEATING PLANS, EXIT SIGNS AND/NOR FIRE
 EXTINGUSIHERS.
  
  
 PLEASE PROVIDE DETAILS.
  
  
 6) WILL THERE BE GENERATOR POWER AND NIGHTTIME
 OCCUPANCY REQUIRING ELECTRICAL CORDS THROUGHOUT THE
 TENT STRUCTURE?
  
 PLEASE PROVIDE DETAILS.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED WITH
 RESUBMITTAL.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  