Plan Review Notes
Plan Review Notes For Permit 19100116
Permit Number 19100116
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-03 09:42:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. APPLICATION SHALL BE MADE BY A CERTIFIED BUILDING
 CONTRACTOR (CBC) OR A CERTIFIIDE GENERAL CONTRACTOR
 (CGC) LICENSED BY THE STATE OF FLORIDA AND REGISTERED
 WITH THE JURISDITION WHERE THE WORK WILL BE PERFORMED.
 PERMITS
 105.1 REQUIRED.
  
 2. TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN OF
 40 FEET OR GREATER IN ANY DIRECTION SHALL BE EVALUATED
 BY A LICENSED FLORIDA ARCITECT OR ENGINEER. EVALUATION
 AND CONNECTION DETAILS SHALL BE SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL. (SEE TEMPORARY MEMBRANE
 STRUCTURES CHECKLIST BELOW).
 2017 FBC CHAPTER 31
 SPECIAL CONSTRUCTION
  
 SECTION 3103
 TEMPORARY STRUCTURES
  
 3103.1 GENERAL. THE PROVISIONS OF SECTIONS 3103.1
 THROUGH 3103.4 SHALL APPLY TO STRUCTURES ERECTED FOR A
 PERIOD OF LESS THAN 180 DAYS. TENTS AND OTHER MEMBRANE
 STRUCTURES ERECTED FOR A PERIOD OF LESS THAN 180 DAYS
 SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE.
 THOSE ERECTED FOR A LONGER PERIOD SHALL COMPLY WITH
 APPLICABLE SECTIONS OF THIS CODE.
 3103.1.1 CONFORMANCE. TEMPORARY STRUCTURES AND USES
 SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY,
 MEANS OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
 3103.1.2 PERMIT REQUIRED. TEMPORARY STRUCTURES THAT
 COVER AN AREA GREATER THAN 120 SQUARE FEET (11.16 M2),
 INCLUDING CONNECTING AREAS OR SPACES WITH A COMMON
 MEANS OF EGRESS OR ENTRANCE THAT ARE USED OR INTENDED
 TO BE USED FOR THE GATHERING TOGETHER OF 10 OR MORE
 PERSONS, SHALL NOT BE ERECTED, OPERATED OR MAINTAINED
 FOR ANY PURPOSE WITHOUT OBTAINING A PERMIT FROM THE
 BUILDING OFFICIAL.
 3103.2 CONSTRUCTION DOCUMENTS. A PERMIT APPLICATION AND
 CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED FOR EACH
 INSTALLATION OF A TEMPORARY STRUCTURE. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE A SITE PLAN INDICATING THE
 LOCATION OF THE TEMPORARY STRUCTURE AND INFORMATION
 DELINEATING THE MEANS OF EGRESS AND THE OCCUPANT LOAD.
 3103.3 LOCATION. TEMPORARY STRUCTURES SHALL BE LOCATED
 IN ACCORDANCE WITH THE REQUIREMENTS OF TABLE 602 BASED
 ON THE FIRE-RESISTANCE RATING OF THE EXTERIOR WALLS FOR
 THE PROPOSED TYPE OF CONSTRUCTION.
 3103.4 MEANS OF EGRESS. TEMPORARY STRUCTURES SHALL
 CONFORM TO THE MEANS OF EGRESS REQUIREMENTS OF CHAPTER
 10 AND SHALL HAVE AN EXIT ACCESS TRAVEL DISTANCE OF 100
 FEET (30 480 MM) OR LESS.
  
 APPLICANTION CHECKLIST
 ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS,
 GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS
 * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS
 PRIOR TO EVENT
 1. PERMIT APPLICATION
 A. PROVIDE EVENT FUNCTION
  B. ADDRESS OF EVENT
  C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS
 D. OWNER AND CONTRACTOR INFO.
  E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER
  F. SPECIFY DATES OF INSTALLATION AND REMOVAL
 2. SITE PLAN
  A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE?
  B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER
 FBC CHPT. 6, SEC. 602
  C. PROVIDE SQUARE FOOTAGE
  D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT
  E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT
 ENTRANCE
  F. IDENTIFY MEANS OF EGRESS PER CHPT. 10
  G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE
 RESTROOMS
  H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500
 FEET OF TENT
 2. FOUNDATION/TIE DOWN
  A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT
  B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL
 MOVEMENT
 3. CONFORMANCE PER SECTION 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D) PROVIDE FLOOR LAYOUT OF EVENT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.
 _______________________________________________________
 _________________
  
  
 *ADDITIONAL REQUIREMENTS
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 OPTION TO ABOVE REQUIREMENT ?
 YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT
 WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH
  
 _______________________________________________________
 _________________
  
  
 **ADDITIONAL REQUIREMENTS
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN
 OF 40 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 NO EXCEPTIONS
  
 _______________________________________________________
 _________
  
  
 3. TEMPORARY MEMBRANE STRUCTURES WITH A FLOOR SPACE OF
 5000 SQ. FT. OR GREATER AND AN OCCUPANCY RATING OF 500
 OR MORE SHALL BE CONSIDERED A THRESHOLD STRUCTURE AND
 SHALL REQUIRE A SPECIAL INSPECTOR. (SEE GUIDELINES FOR
 SPECIAL INSPECTORS BELOW).
 FBC 110.8 THRESHOLD BUILDING.
 110.8.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLANS IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL
 INSPECTOR MAY NOT SERVE AS A SURROGATE IN CARRYING OUT
 THE RESPONSIBILITIES OF THE BUILDING OFFICIAL, THE
 ARCHITECT OR THE ENGINEER OF RECORD. THE CONTRACTOR'S
 CONTRACTUAL OR STATUTORY OBLIGATIONS ARE NOT RELIEVED
 BY ANY ACTION OF THE SPECIAL INSPECTOR.
  
 CONFORMING TO CHAPTER 553 FLORIDA STATUTES,
 CHAPTER 468, PART XII, FLORIDA STATUTES
 AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF
 WEST PALM BEACH
  
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; A COPY OF THE CURRENT SPECIAL
 INSPECTOR AGREEMENT HAS BEEN UPLOADED INTO THIS
 SUBMITTAL ON PROJECT DOX FOR YOUR REVIEW AND USE.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) -
 ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT
 IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT.
 SUGGESTED:
  
 REQUIRED FOR ALL
  
 "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633."
  
 4. PROVIDE A COPY OF THE FLAME SPREAD TEST REPORT FOR
 EACH MEMBRANE STRUCTURE. E-84 OR EQUIVALENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
  