2019-10-07 05:17:58 | 1) THE LETTER FOR THE ALTERNATE APPROVAL FOR THE DRAIN |
| TO A DRYWELL IS FOR SHOWER EFFLUENT BUT THE SUBMITTED |
| "DETAIL E" NOTES THE DRAIN FROM A DRINKING FOUNTAIN. |
| WHICH IS IT? CLARIFY. A REVISED LETTER WILL BE REQUIRED |
| OR A REVISED DETAIL IF IT FOR A SHOWER. |
| 2) THE LETTER FOR THE ALTERNATE APPROVAL OF THE DRAIN |
| TO THE DRYWELL AND THE CORRESPONDING DETAIL SHALL BEAR |
| THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL PER |
| FL. ADMIN. CODE RULE 61G15-23.001. |
| 3) TWO DIFFERENT SPECIFICATIONS HAVE BEEN SUBMITTED FOR |
| THE DRINKING FOUNTAINS ( 1035 SMSS & 10155 SM). WHICH |
| UNIT IS BEING INSTALLED. CLARIFY. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 4) SHT.L3.11 - DETAIL "C" - THE MAXIMUM HEIGHT TO THE |
| BOTTLE FILLER CONTROLS AND BOTTLE SHELF SHALL BE 48 |
| INCHES PER THE 2017 FBC-ACCESSIBILITY SECS.308.2, |
| 308.3, 309. |
| 5) SHT.L3.11 - DETAIL "C"- THE MAXIMUM HEIGHT OF THE |
| WATER SPOUT SHALL BE 36 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND PER 2017 FBC-ACCES. SEC. 602.4 FOR |
| ACCESSIBLE FOUNTAINS FOR USE BY PEOPLE IN WHEELCHAIRS. |
| MODEL 10155 SM DOES NOT COMPLY AS SHOWN ON THIS DETAIL. |
| 6) THE DETAIL FOR DRINKING FOUNTAIN 10155 SM SHOWN ON |
| SHT. L3.11 DOES NOT CORRELATE WITH THE MANUFACTURER'S |
| SPECIFICATION SHEET THAT HAS BEEN SUBMITTED FOR THIS |
| SAME MODEL IN REGARDS TO THE HEIGHT OF THE DRINKING |
| FOUNTAIN ABOVE THE FINISH FLOOR OR GROUND. CLARIFY. |
| 7) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| PERSONS SHALL BE 38 INCHES MINIMUM AND 43 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER 2017 FBC- |
| ACCESS. SEC. 602.7. |
| 8 ) THE HEIGHT OF THE SPOUT FOR PEOPLE IN WHEELCHAIRS |
| SHALL BE LOCATED A MAXIMUM OF 36 INCHES ABOVE THE |
| FINISH FLOOR OR GROUND. REFER TO THE MANUFACTURER'S |
| SPECIFICATION SHEET FOR MODEL 10135 SMSS. |
| 9) WHO IS THE MANUFACTURER FOR DRINKING FOUNTAIN MODEL |
| 10135 SMSS? THE IS NO MANUFACTURER LISTED ON THE |
| SPECIFICATION SHEET. CLARIFY.SUBMIT SPEC SHEET THAT |
| SHOWS THE MANUFACTURER.WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) ALL PLUMBING PRODUCTS AND MATERIALS SHALL BE LISTED |
| BY A THIRD- PARTY CERTIFICATION AGENCY AS COMPLYING |
| WITH THE REFERENCED STANDARDS. THE SUBMITTED |
| SPECIFICATION SHEETS FOR THE DRINKING FOUNTAINS OR THE |
| SHOWER DO NOT SHOW ANY TYPE OF LISTING OR |
| CERTIFICATION.SUBMIT SPECIFICATION SHEETS THAT COMPLY. |
| 11) THE SUBMITTED SPECIFICATION SHEETS FOR THE SHOWER |
| SHOW THE HEIGHT OF THE SHOWER CONTROLS IN SI UNITS OF |
| MEASUREMENT ( MILLIMETERS? ). SHOW THE HEIGHT OF THE |
| SHOWER CONTROL IN U.S. CUSTOMARY SYSTEM UNITS OF |
| MEASUREMENT. WPB AMEND. TO FBC SEC. 107.2.1.THE HEIGHT |
| OF THE CONTROL SHALL COMPLY WITH THE 2017 FBC- ACCESS. |
| SECS. 308 & 309. |
| 12) RESPONSE #2 OF THE RESPONSE NARRATIVE REFERS TO |
| CORRESPONDENCE FROM THE MANUFACTURER OF THE DRINKING |
| FOUNTAINS INDICATING COMPLIANCE WITH THE FLORIDA |
| ACCESSIBILITY CODE. THERE IS NO SUCH CORRESPONDENCE IN |
| THE SUBMITTAL PACKAGE. CLARIFY. |
| |