Notes
Date Text
2019-10-10 15:34:241ST REVIEW: 19091159
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-1 PAGE IS TO CONGESTED TO DETERMINE CODE
 COMPLIANCE PLEASE SEPARATE THE THE SANITARY ISOMETRIC
 DRAWING FROM THE FLOOR PLAN. PER WPB AMEND TO FBC
 107.3.5.3(12)
  
 2. SHT P-1 THE SANITARY RISER IS NOT CODE COMPLIANT
 PLEASE CORRECT THE FOLLOWING ISSUES.
 A)THE 3" VENT IN ALL THREE BATHROOM GROUPS APPEARS TO
 BE A HORIZONTAL DRY VENT WHICH IS NOT ALLOWED BY CODE
 THESE VENT ARE NOT REQUIRED VENTS THE VENTS ON THE
 LAVATORY CAN SERVE AS THE VENT FOR THE BATHROOM GROUP.
 PER FBC RES P3108.1
 B) THE LAVATORY IN BATHROOM #2 SHALL CONNECT BETWEEN
 THE TOILET AND THE SHOWER TO CREATE A CODE COMPLIANT
 WET VENT SYSTEM. PER FBC RES P3108.1
  
 3. PLEASE PROVIDE SIZING CALCULATIONS FOR ROOF DRAINS .
 PER WPB AMEND TO FBC 107.2.1 SHALL COMPLY WITH FBC RES
 R903.4.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  