Date |
Text |
2019-10-07 08:20:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| 2. PROVIDE NOTE ON PLANS STATING GENERATOR WILL BE |
| UNDER A SEPARATE PERMIT. FBC 107.2.1 FBC 105.1 |
| |
| 3. DISHWASHER MUST BE AFCI AND GFCI PROTECTED. NEC |
| 210.12, 210.8D |
| |
| 4.RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| |
| 5. 2 TANKLESS WATER HEATER SHOWN ON PLAN. ARE THEY GAS |
| OR ELECTRIC? PLEASE SPECIFY. IF ELECTRIC THAN THEY MUST |
| BE INCLUDED IN LOAD CALCULATION. FBC 107.2.1 |
| |
| 6. ALARMS OUTSIDE BEDROOMS MUST ME CO/SMOKE COMBOS. |
| PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| |
| 7. RECEPTACLE REQUIRED AT REAR OF DWELLING. NEC |
| 210.52E1 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| |