Plan Review Notes
Plan Review Notes For Permit 19091144
Permit Number 19091144
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-12-09 13:47:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INDICATIONS OF UNDERGROUND FIRE LINE, IS IT
 EXISTING OR IS IT NEW.
  
 ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWING.
  
  
 1A.) IS THIS A DEDICATED FIRE LINE OR IS IT TIED INTO
 THE DOMESTIC LINE?
  
 IF THE WATER TO THE BLDG IS CUT OFF, WILL THE FS SYSTEM
 REMAIN WET.
  
 PLEASE PROVIDE DETAILS.
  
  
 2) THERE IS NO INDICATION OF A DDCV.
  
 WHERE IS THE DDCV LOCATED AND PROVIDED THE
 SPECIFICATION SHEETS INDICATING LEAD-FREE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  