Plan Review Notes For Permit 19091144 |
Permit Number |
19091144 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-12-09 13:47:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS INDICATIONS OF UNDERGROUND FIRE LINE, IS IT | | EXISTING OR IS IT NEW. | | | | ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER | | SEPARATE PERMIT AND SHOP DRAWING. | | | | | | 1A.) IS THIS A DEDICATED FIRE LINE OR IS IT TIED INTO | | THE DOMESTIC LINE? | | | | IF THE WATER TO THE BLDG IS CUT OFF, WILL THE FS SYSTEM | | REMAIN WET. | | | | PLEASE PROVIDE DETAILS. | | | | | | 2) THERE IS NO INDICATION OF A DDCV. | | | | WHERE IS THE DDCV LOCATED AND PROVIDED THE | | SPECIFICATION SHEETS INDICATING LEAD-FREE. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|