2019-10-01 15:15:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO HYDRAULIC CALCULATIONS PROVIDED.
  
 PLEASE PROVIDE.
  
  
  
 2) NFPA 13 PROVIDES THE FOLLOWING:
  
 22.17 HEALTH CARE FACILITIES CODE, HYPERBARIC CHAMBERS.
 22.17.1 DESIGN REQUIREMENTS.
 22.17.1.1 A FIXED WATER DELUGE EXTINGUISHING SYSTEM
 SHALL BE
 INSTALLED IN ALL CHAMBER COMPARTMENTS THAT ARE DESIGNED
 FOR
 MANNED OPERATIONS.
 22.17.1.2 IN CHAMBERS THAT CONSIST OF MORE THAN ONE
 CHAMBER
 COMPARTMENT (LOCK), THE DESIGN OF THE DELUGE SYSTEM
 SHALL
 MEET THE REQUIREMENTS OF 22.17.1.1 WHEN THE CHAMBER
 COMPARTMENTS
 ARE AT DIFFERENT DEPTHS (PRESSURES).
 22.17.1.3 THE DELUGE SYSTEM IN DIFFERENT COMPARTMENTS
 (LOCKS)
 SHALL OPERATE INDEPENDENTLY OR SIMULTANEOUSLY.
 22.17.1.4 FIXED DELUGE SYSTEMS SHALL NOT BE REQUIRED IN
 CHAMBER
 COMPARTMENTS THAT ARE USED STRICTLY AS PERSONNEL
 TRANSFER
 COMPARTMENTS (LOCKS) AND FOR NO OTHER PURPOSES.
 22.17.1.5* MANUAL ACTIVATION AND DEACTIVATION DELUGE
 CONTROLS
 SHALL BE LOCATED AT THE OPERATOR?S CONSOLE AND IN EACH
 CHAMBER
 COMPARTMENT (LOCK) CONTAINING A DELUGE SYSTEM.
 22.17.1.6 CONTROLS SHALL BE DESIGNED TO PREVENT
 UNINTENDED
 ACTIVATION.
 22.17.1.7 WATER SHALL BE DELIVERED FROM THE FIXED
 DISCHARGE
 NOZZLES AS SPECIFIED IN 22.17.1.9 WITHIN 3 SECONDS OF
 ACTIVATION
 OF ANY AFFILIATED DELUGE CONTROL.
 22.17.1.8* AVERAGE SPRAY DENSITY AT FLOOR LEVEL SHALL
 BE NOT LESS
 THAN 2 GPM/FT2 (81.5 L/MIN/M2), WITH NO FLOOR AREA
 LARGER THAN
 10.76 FT2 (1M2) RECEIVING LESS THAN 1 GPM/FT2 (40.75
 L/MIN/M2).
 22.17.1.9 WATER SHALL BE AVAILABLE IN THE DELUGE SYSTEM
 TO
 MAINTAIN THE FLOW SPECIFIED IN 22.17.1.8 SIMULTANEOUSLY
 IN
 EACH CHAMBER COMPARTMENT (LOCK) CONTAINING THE DELUGE
 SYSTEM
 FOR 1 MINUTE.
 22.17.1.10 THE LIMIT ON MAXIMUM EXTINGUISHMENT DURATION
 SHALL BE GOVERNED BY THE CHAMBER CAPACITY (BILGE
 CAPACITY ALSO, IF
 SO EQUIPPED) OR ITS DRAINAGE SYSTEM, OR BOTH.
 22.17.1.11 THE DELUGE SYSTEM SHALL HAVE STORED PRESSURE
 TO
 OPERATE FOR AT LEAST 15 SECONDS WITHOUT ELECTRICAL
 BRANCH
 POWER.
  
  
 PLEASE CORRECT OR PROVIDE DETAILED JUSTIFICATION
 MEETING COMPLIANCE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  