Plan Review Notes
Plan Review Notes For Permit 19091122
Permit Number 19091122
Review Stop M
Sequence Number 4
Notes
Date Text
2019-11-25 11:53:512ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19091122
 11/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SHEETS M3, P3, & E3 HAVE NOT BEEN CORRECTED. THE
 STORAGE MEZZANNE IS STILL IDENTIFIED AS AN ATTIC- SEE
 COMMENT BELOW.
  
 1) SHEET M-3: THE EXISTING STORAGE MEZZANINE IS NOW
 IDENTIFIED AS AN "ATTIC". PLEASE SEE SECTION 202 FBC EC
 WHICH DEFINES ATTICS AS ENCLOSED UNCONDITIONED SPACES
 ABOVE CEILINGS. THIS AREA IS CONDITIONED, IT'S SQUARE
 FOOTAGE HAS BEEN ADDED TO THE REVISED ENERGY
 CALCULATIONS (TOTAL 11208 SF), AND THE REVISED AC
 CALCULATION FOR RTU- 2 INDICATES VENTILATION CFMS FOR
 OCCUPANTS. PLEASE CLARIFY THE USE OF THE SPACE, AND
 CORRECT THE IDENTIFICATION ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  