2019-12-02 14:22:10PLUMBING PROVISO:
  
 PLUMBING COMMENTS: SHALL COMPLY PRIOR TO 2ND ROUGH
 INSPECTION.
  
 1. THE SHOWER GRAB BARS SHALL COMPLY WITH FBC ACC
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM
 FROM ADJACENT WALLS.
 2. ALL GRAB BARS SHALL COMPLY WITH FBC ACC 609.4
 POSITION OF GRAB BARS.GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 3. THE ICE MAKER SHALL HAVE A BACKFLOW DEVICE ON SUPPLY
 LINE. PER FBC PL 608.3
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
 5. HOT WATER PIPING SHALL BE INSULATED WITH 1? WALL
 THICKNESS INSULATION. PER FBC ENER. TABLE C403.2.10
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  