Plan Review Notes For Permit 19091122 |
Permit Number |
19091122 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-12-02 14:22:10 | PLUMBING PROVISO: | | | | PLUMBING COMMENTS: SHALL COMPLY PRIOR TO 2ND ROUGH | | INSPECTION. | | | | 1. THE SHOWER GRAB BARS SHALL COMPLY WITH FBC ACC | | 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. | | WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE | | SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE | | BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB | | BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT | | IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER | | COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE | | WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM | | FROM ADJACENT WALLS. | | 2. ALL GRAB BARS SHALL COMPLY WITH FBC ACC 609.4 | | POSITION OF GRAB BARS.GRAB BARS SHALL BE INSTALLED IN A | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, | | 3. THE ICE MAKER SHALL HAVE A BACKFLOW DEVICE ON SUPPLY | | LINE. PER FBC PL 608.3 | | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5 | | 5. HOT WATER PIPING SHALL BE INSULATED WITH 1? WALL | | THICKNESS INSULATION. PER FBC ENER. TABLE C403.2.10 | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|