2019-10-21 16:31:25 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19091122 |
| REVIEWED: OCTOBER 21, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 505 FBC[EXISTING]PLEASE CHANGE LEVEL OF ALTERATION |
| TO LEVEL 3 ON SHEET ALS1.1 SINCE ALTERATIONS OCCUR IN |
| MORE THAN 50% OF THE BUILDING AREA. |
| |
| 2) 501 GENERAL AREA. |
| THE SQ. FOOTAGE VARIES FROM PAPA AT 9792, SHEET ALS1.1 |
| AT 9140 AND ENERGY CALCS AT 10,979. PLEASE GIVE AN |
| OVERALL SQ. FOOTAGE FOR AREA CALCULATION. THE AREA SQ. |
| FOOTAGE CAN EXCLUDE THE MEZZANINE IF IT MEETS THE |
| REQUIREMENTS (SEE COMMENTS 4 AND 5). THE LIFE SAFETY |
| OCCUPANCY SQ. FOOTAGE CAN REMAIN AS SHOWN ON SHEET |
| ALS1.1. |
| ADJUST SQ. FOOTAGE ON ENERGY CALCS IF APPLICABLE. |
| ALSO, THE ENERGY CALCULATIONS INCLUDE NO INPUT DATA FOR |
| FLOORS, WALLS, WINDOWS, DOORS, SKYLIGHTS AND ROOF. I |
| HAVE NO DATA FOR INSULATION ON ROOF OR WALLS. PLEASE |
| PROVIDE DATA FOR BUILDING ENVELOPE. |
| |
| 3) TABLE 506.2 ALLOWS 9000 SQ. FT. FOR OCCUPANCY B TYPE |
| V-B CONSTRUCTION. IT APPEARS THAT YOU WOULD LIKE THE |
| MEZZANINE TO NOT COUNT TOWARDS THAT SQUARE FOOTAGE |
| LIMIT, SO PLEASE SHOW DETAILS THAT THE MEZZANINE MEETS |
| ALL CRITERIA FOR A MEZZANINE. |
| |
| 4) 505.2 MEZZANINES. A MEZZANINE OR MEZZANINES IN |
| COMPLIANCE WITH SECTION 505.2 SHALL BE CONSIDERED A |
| PORTION OF THE STORY BELOW. SUCH MEZZANINES SHALL NOT |
| CONTRIBUTE TO EITHER THE BUILDING AREA OR NUMBER OF |
| STORIES AS REGULATED BY SECTION 503.1. THE AREA OF THE |
| MEZZANINE SHALL BE INCLUDED IN DETERMINING THE FIRE |
| AREA. THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE |
| FLOOR CONSTRUCTION SHALL BE NOT LESS THAN 7 FEET (2134 |
| MM). |
| -WHAT IS THE CEILING HEIGHT IN MEZZANINE AREA? |
| |
| 5) 505.2.3 OPENNESS. A MEZZANINE SHALL BE OPEN AND |
| UNOBSTRUCTED TO THE ROOM IN WHICH SUCH MEZZANINE IS |
| LOCATED EXCEPT FOR WALLS NOT MORE THAN 42 INCHES (1067 |
| MM) IN HEIGHT, COLUMNS AND POSTS. |
| -IS THE MEZZANINE OPEN TO THE AREA THAT IT SERVES? |
| PLEASE SHOW DETAILS OF WHAT THE INTERIOR WALL CONSISTS |
| OF ON THE MEZZANINE LEVEL. I SEE A DETAIL FOR MEZZANINE |
| RAILING ON A3.1.2, BUT I DON?T SEE IT CALLED OUT ON |
| PLANS. |
| |
| PROVISOS: |
| A)DEFERRED SUBMITTALS-INTERIOR GLASS WALL SYSTEM, |
| ROOFING(WITH SUB-PERMIT APPLICATION) AND SKYLIGHTS |
| B)SEPARATE PERMITS REQUIRED FOR- |
| LOW VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION. |
| C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE |
| PLANS AT FINAL STAMPING. |
| |
| PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |