Plan Review Notes
Plan Review Notes For Permit 19091105
Permit Number 19091105
Review Stop M
Sequence Number 6
Notes
Date Text
2020-05-28 15:57:33MECHANICAL REVIEW APPROVED WITH PROVISO:
 1- BALANCED RETURN AIR DUCT TO BE 12" MIN. AS REQUIRED
 BY SEC. M1602.3 FBC-RESIDENTIAL EXCEPTION #3.
 2- REVISE LOAD CALCULATIONS. ENTRY DOOR DOESN'T FACE
 WEST. SEE PLANS AND REVISE AS REQUIRED.
2020-05-28 11:35:28NEW SET OF PLANS SUBMITTED. JG.