Plan Review Notes For Permit 19091105 |
Permit Number |
19091105 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2020-03-24 09:51:35 | 3RD REVIEW FBC-2017 MECHANICAL | | PERMIT #19091105 | | 3/24/20 | | | | CODES IN EFFECT: | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL | | EXISTS- PLEASE COMPLY. | | | | 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A | | TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET | | AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. | | LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO | | PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL. | | STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|