Plan Review Notes
Plan Review Notes For Permit 19091105
Permit Number 19091105
Review Stop B
Sequence Number 3
Notes
Date Text
2019-12-19 09:33:4312/18/19 MET WITH CHRISTOPHER BACHE (CONTRACTOR). HE
 AGREED TO PASS BUILDING REVIEWS WITH PROVISO. JG.
  
 12/19/19 DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL.
  
  
  
 ********PREVIOUS COMMENTS:
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- ENERGY CALCULATIONS:
 A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON
 PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4
 DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND
 JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD
 DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
  
 2- SURVEY SUBMITTED:
 HOUSE FOOTPRINT SHOWN ON THE NEW SURVEY SUBMITTED
 DOESN'T MATCH HOUSE FOOTPRINT OF PLANS SUBMITTED. PLANS
 ARE FOR A 5 BEDROOM HOUSE. NEED TO COORDINATE PLANS AND
 SURVEY. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- OK
  
 4- OK
  
 5- OK
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 ONLY ONE PRODUCT APPROVAL WAS SUBMITTED. NEED TWO. SEC.
 107.1 CITY AMENDMENTS.
  
 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 8- OK
  
 9- OK
  
 10-IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]