Date |
Text |
2019-12-13 14:08:55 | PLAN REVIEW - MECHANICAL |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| |
| 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET |
| AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. |
| LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO |
| PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL. |
| STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC. |
| (NOT ADDRESSED) |
| |
| 2) CORRECTED |
| |
| 3) CORRECTED |
| |
| 4) AC-1: INDICATE THE SIZE OF THE DUCT FROM THE RAG TO |
| THE AIR HANDLER- SECTION M1602.2 FBC RES. (PARTIAL |
| CORRECTION) |
| |
| 5) AC-1: THE RETURN TRANSFER DUCTS FROM BEDROOMS 3, 4, |
| & 5 ARE UNDERSIZED PER SECTION M1602.3 FBC RES- THE |
| RETURN DUCT DIAMETERS SHALL BE 1.5 TIMES THE DIAMETERS |
| OF THE SUPPLY DUCTS. (NOT ADDRESSED) |
| |
| 6) AC-1 EXHAUST VENTILATION AT A RATE OF 100 CFMS |
| INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED |
| FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE |
| SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND |
| M1503.4 FOR MAKEUP AIR. (NOT ADDRESSED) |
| |
| 7) AC-1 VERIFY COMPLIANCE WITH SECTION R403.3.6 |
| AIR-HANDLING UNITS IN ATTICS: (NOT ADDRESSED) |
| |
| AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| CONDITIONS ARE MET: |
| |
| 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| |
| 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN |
| THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| |
| 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER. |
| |
| 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |
| |
| 8) AC-1: PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| M1305.1.4.1 AND M1401.4 FBC RES. (DETAIL PROVIDED - |
| PLAN PAGE MISSING SIGNATURE AND SEAL OF DESIGN |
| PROFESSIONAL) |
| |
| |