Plan Review Notes For Permit 19091104 |
Permit Number |
19091104 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2020-03-23 14:51:26 | BUILDING REVIEW APPROVED WITH PROVISO: | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | INSPECTIONS TO AVOID CONFLICTS/DELAYS) | | | | 1-REVISE ENERGY CALCULATIONS: | | A) REVISE # OF BEDROOMS AND CONDITIONED FLOOR AREA TO | | MATCH PLANS. | | B) PROVIDE THE BUILDER'S NAME. | | C) REVISE DOORS INFORMATION. THERE ARE NO DOORS ON THE | | WEST SIDE AND THERE ARE NO WOOD DOORS. | | D) REVISE WINDOWS ORIENTATION AND AREA TO MATCH PLANS. | | | | 2- REVISE SURVEY TO MATCH PROPOSED RESIDENCE. NO MIRROR | | IMAGE AND ALL DIMENSIONS TO MATCH PLANS. PROVIDE ACTUAL | | FOOTPRINT THAT MATCHES PLANS. | | | | 3- REVISE DRAINAGE PLAN: THE FOOTPRINT OF THE HOUSE | | DOESN'T MATCH THE PROPOSED HOUSE. NO MIRROR IMAGE. | | PROVIDE ACTUAL FOOTPRINT THAT MATCHES PLANS. |
|