2020-02-12 13:07:51 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #19091104 |
| 2/12/20 |
| |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| SHEET AC-1: THE AC PLANS HAVE BEEN RESUBMITTED WITHOUT |
| THE SIGNATURE OF THE CONTRACTOR, OR THE SIGNATURE AND |
| SEAL AND TITLE BLOCK OF THE FL. LICENSED DESIGN |
| PROFESSIONAL WHO PREPARED THE DRAWING. SEE COMMENT #1 |
| FROM THE 1ST & 2ND REVIEWS PRINTED BELOW. |
| |
| 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET |
| AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. |
| LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO |
| PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL. |
| STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |