Date |
Text |
2019-12-11 09:50:32 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| 1- ENERGY CALCULATIONS: |
| A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY |
| CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1 |
| FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON |
| PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| B) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 |
| DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND |
| JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| D) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE |
| ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD |
| DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| E) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH |
| PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| |
| 2- OK |
| |
| 3- OK |
| |
| 4-OK |
| |
| 5- OK |
| |
| 6- OK |
| |
| 7- OK |
| |
| 8- OK |
| |
| 9-OK |
| |
| 10-IMPACT FEES - |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK |
| OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. |
| PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT |
| AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |