2019-10-16 10:56:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE |
| CONDUCTORS MUST HAVE OVERCURRENT PROTECTION WHERE THEY |
| ENTER THE DWELLING UNIT. SERVICE CONDUCTORS ARE NOT |
| PERMITTED TO EXTEND FURTHER THAN 8 FEET INTO A |
| STRUCTURE WITHOUT OVERCURRENT PROTECTION. IF THIS |
| OVERCURRENT PROTECTION IS LOCATED ON THE EXTERIOR OF |
| THE DWELLING, THAN THE CONDUIT TO THE INTERIOR PANEL |
| MUST INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. IF THE |
| CONDUCTORS ARE RUN UNDERGROUND FROM THE METER TO THE |
| INTERIOR PANEL, AND THAT PANEL HAS A MAIN BREAKER, THE |
| CONDUCTORS MUST NOT EXCEED 8 FEET IN LENGTH BEFORE |
| TERMINATION TO THE MAIN BREAKER. PROVIDE CLARIFICATION |
| AND/OR CORRECTION. NEC 230.70, 250.122; FBC RE E3601.6, |
| E3704.6, 3607.3.1 |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 3. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| 4. NOTE 12 STATES THAT LIGHTING IN CLOTHES CLOSETS |
| SHALL COMPLY WITH NEC 410.8, WHICH IS NOT THE CORRECT |
| CODE. PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 |
| 5. NOTE 18 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE E4002.14 |
| 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |