Plan Review Notes
Plan Review Notes For Permit 19091100
Permit Number 19091100
Review Stop G
Sequence Number 2
Notes
Date Text
2020-01-02 11:20:551) INDICATE THE DELIVERY PRESSURE ( PSI ) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.2ND
 REQUEST.
 2 ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. SECOND REQUEST.
 3) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE
 POOL HEATER IN RELATION TO BUILDING OPENINGS (SOFFITS)
 AND OPERABLE DOORS AND WINDOWS. THE POOL HEATER EXHAUST
 SHALL BE LOCATED PER THE POOL HEATER INSTALLATION
 MANUAL.SECOND REQUEST.
 4) THE POOL HEATER SHALL HAVE A THERMAL EFFICIENCY
 RATING OF 82% PER THE 2017 FBC-ENERGY SEC.
 R403.10.4.THE SUBMITTED SPECIFICATIONS FOR THE POOL
 HEATER DO NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER
 SPECS THAT SHOW THE REQUIRED THERMAL EFFICIENCY. THE
 SPECS ARE NOT ON FILE WITH THE CITY.
 5) INDICATE ON THE GAS RISER DRAWING IF ANY PIPE WILL
 BE INSTALLED UNDERGROUND AND IF SO, NOTE THE TYPE OF
 PIPING ON THE GAS RISER. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  