2019-10-02 06:47:07 | 1) ONE OF THE GAS PLANS HAS BEEN DRAWN IN PENCIL. |
| PENCIL IS NOT AN ACCEPTABLE FORMAT. SUBMIT TWO COPIES O |
| A GAS DRAWN IN A NON - ERASABLE FORMAT. WPB AMEND. TO |
| FBC SEC. 107.1. |
| 2) THE PERMIT APPLICATION DESRCIBES THE SCOPE OF WORK |
| AS INSTALLING A GAS LINE TO A POOL HEATER BUT THE GAS |
| DRAWING SHOWS A GENERATOR. CLARIFY. |
| 3) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| FBC-R SEC. G2413.4.1, G2413.4.2. |
| 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21). |
| 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| SEC. G 2413.4.1, G2413.4.2. |
| 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| 8) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| 9) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| 10) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE |
| POOL HEATER IN RELATION TO BUILDING OPENINGS (SOFFITS) |
| AND OPERABLE DOORS AND WINDOWS. THE POOL HEATER EXHAUST |
| SHALL BE LOCATED PER THE POOL HEATER INSTALLATION |
| MANUAL. |
| |