2019-10-24 07:24:34 | 10/23 - SPOKE W/APPLICANT, GAVE OPTIONS. NUCORE |
| (LAMINATE) WAS SUBMITTED, SPEC SHEET SHOWS COMPLIANCE |
| BUT WAS TESTED WITH A DROPPED CEILING, APPEARS THAT |
| THIS PRODUCT ALONE WILL NOT MEET STC/IIC REQUIREMENTS. |
| WHISPERMAT HW WAS ALSO SUBMITTED AS PROPOSED |
| UNDERLAYMENT; WE HAVE STC/IIC ON FILE BUT NO FLAME |
| SPREAD. ADVISED APPLICANT TO CONTACT WHISPERMAT |
| TECHNICAL REP AND OBTAIN FLAME SPREAD TEST IF |
| AVAILABLE. [email protected] |
| |
| |
2019-10-22 08:42:11 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC B 1207.2, 1207.3 PLEASE NOTE THAT TEST REPORTS |
| ARE REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT |
| ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| SELECTED; THIS IS A GENERAL COMMENT). SECOND REQUEST. |
| 2. FBC B 1207.2, 1207.3 THE TEST REPORT CANNOT INCLUDE |
| A DROPPED GYPSUM CEILING. PROVIDE A COPY OF THE TEST |
| REPORT. SECOND REQUEST. |
| 3. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. SECOND REQUEST. |
| |