2019-09-27 09:07:341ST REVIEW: 19091009
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH KNEE AND TOE CLEARANCE
 FOR ALL THE ACCESSIBLE LAVATORY'S. PER FBC ACC 306.2,
 306.3
  
 2. LABEL ALL THE CLEAR FLOOR SPACES WITH REQUIRED
 DIMENSIONS. PER FBC ACC 305, 604.3.1
  
 3.PROVIDE COMPLIANCE FOR THE THE WATER FOUNTAIN. PER
 FBC ACC 602.4, 602.7,602.2
  
 4. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. PER
 FBC ACC 604.7
  
 5. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. PER FBC ACC 604.4
  
 6. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
 COMPARTMENTS COMPLYING WITH 604.8.2. PER FBC ACC 604.6
  
 7. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 8. SHT. PS.0.0 THE DETAIL FOR THE WATER HEATER NOTE #8
 SHOWS 140 DEQ. WATER AND THE PIPING IS LABELED AT 110
 DEQ. PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. PS.0.0 THE WATER HEATER DETAIL SHOWS A
 RECIRCULATION PUMP WITH PIPING THE WATER ISOMETRIC ON
 SHT PS.0.3 DOES NOT SHOW ONE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 10. BACKFLOW DEVICE IS REQUIRED ON THE ICE MAKER
 SUPPLY. PER FBC PL 608.3
  
 11. PROVIDE A PLUMBING FIXTURE SCHEDULE. PER WPB AMEND
 TO FBC 107.2.1
  
 12. THE MOP SINK IS NOT VENTED PROPERLY IT SHALL BE
 VENTED BEFORE CONNECTING TO THE BUILDING DRAIN. FBC ACC
 901.2.1
  
 13. THE WATER CLOSETS IN THE FAMILY BATHROOM AND THE
 STANDARD TOILET IN THE WOMENS ARE NOT VENTED IF THE
 BREAK ROOM SINK IS CONNECTED DOWN STREAM OF THE
 BATHROOM GROUP THE TOILETS WILL BE VENTED BY THE WET
 VENT SYSTEM, OR THEY CAN BE SEPARATELY VENTED.PER FBC
 PL 901.2.1, 912.1,912.2.1
  
 14. THE LAVATORY IN THE FAMILY BATHROOM SHALL COMPLY
 WITH FBC ACC 213.3.4,212.3, 606.2, 606.3
  
 15. IN THE FAMILY BATHROOM THERE APPEARS TO BE A SHOWER
 SHT. A4.2 IS SHOWING A SHOWER WITH THE REQUIRED CLEAR
 FLOOR SPACE AND A SHOWER HEAD AND A SHOWER DOOR THE
 DIMENSIONS MEET THE REQUIREMENTS FOR A ALTERNATE ROLL
 IN SHOWER ALL THAT IT WOULD NEED TO MEET THE
 ACCESSIBILITY REQUIREMENTS IS THE INSTILLATION OF GRAB
 BARS, SHTS. PS.0.1-PS.0.3 HAVE THE FIXTURE LABELED AS A
 MOP SINK WITH NO DOOR, IT IS UNCLEAR WHAT THIS FIXTURE
 IS, IF A SHOWER VALVE IS INSTALLED IT SHALL COMPLY WITH
 FBC ACC 608. IF A MOP SINK FAUCET IS INSTALLED AND NO
 SHOWER VALVE IT WILL NOT NEED TO MEET THE ACCESSIBILITY
 REQUIREMENTS.
 IF YOU INTENTION IS FOR THIS FIXTURE TO BE A MOP SINK
 PLEASE PROVIDE A SIGNED AND SEALED LETTER FROM THE
 DESIGN PROFESSIONAL STATING THAT ITS A MOP SINK AND NOT
 A SHOWER OR INSTALL COMPLIANT GRAB BARS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711