2019-09-26 11:47:32 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19091009 |
| 9/26/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET MS.0.1: CONCERNING THE CONDENSING UNITS SHOWN |
| IN THE INTERIOR OF THE BUILDING, PLEASE REFER TO |
| COMMENT #15 FROM THE 1ST MECHANICAL REVIEW ON THE MAIN |
| BUILDING PERMIT #17110075. IN RESPONSE TO THE COMMENT, |
| THE ARCHTITECT REQUESTED A DEFERRED SUBMITTAL TO |
| PROVIDE MANUFACTURER'S CERTIFICATION OF THE OUTDOOR |
| UNITS BEING INSTALLED IN THE INTERIOR OF THE BUILDING. |
| TO DATE THERE HAS NOT BEEN A SUBMITTAL PROVIDED TO |
| ADDRESS THE ISSUE. PLEASE NOTE AC CONDENSERS SHALL BE |
| INSTALLED OUTDOORS IN ACCORDANCE WITH THEIR LISTING AND |
| MANUFACTURER'S SPECIFICATIONS - SECTION 304.1 FBC M. |
| |
| 2) MS.0.1: ASSUMING THE CONDENSERS ARE APPROVED BY THE |
| MANUFACTURER TO BE INSTALLED ON THE INTERIOR AS SHOWN |
| ON THE PLAN, PLEASE SHOW THE REFRIGERANT PIPING RUNS TO |
| THE FROM THE CU'S TO THE AIR HANDLERS- SECTION 107.2.1 |
| WPB. |
| |
| 3) MS.0.1: SHOW THE LOCATION OF THE AIR HANDLER |
| SUPPLYING THE SMALL OFFICES, COPY ROOM, AND THE |
| MEZZANINE- SECTION 107.2.1 WPB. |
| |
| 4) MS.0.1: PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE ON |
| THE PLAN- SECTION 107.2.1 WPB. |
| |
| 5) MS.0.1: THE NEW DDCV DOOR OPENING FROM THE |
| FIRE-RATED STAIRWAY EXTENSION INTO THE ROOM IS NOT |
| ALLOWED PER SECTION1023.3.1 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |