2019-09-27 09:43:15 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE DRINKING FOUNTAINS ARE NOT ALLOWED TO BE |
| INSTALLED IN THE EXIT PASSAGEWAY. FBC 1024.1 EXIT |
| PASSAGEWAYS. EXIT PASSAGEWAYS SERVING AS AN EXIT |
| COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL COMPLY WITH |
| THE REQUIREMENTS OF THIS SECTION. AN EXIT PASSAGEWAY |
| SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS |
| OF EGRESS AND A CIRCULATION PATH. FBC 1024.6 |
| PENETRATIONS. PENETRATIONS INTO OR THROUGH AN EXIT |
| PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND |
| DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION, |
| SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR |
| FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY |
| SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL |
| BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 714. THERE SHALL NOT BE PENETRATIONS OR |
| COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| |
| 2) THE DOOR FROM THE BUSINESS INTO THE EXIT PASSAGEWAY |
| THROUGH THE 2 HOUR FIRE RATED BARRIER WALL IS REQUIRED |
| TO TO HAVE A 90 MINUTE FIRE RATING. FBC TABLE 716.5 |
| |
| 3) THERE ARE ERRORS IN THE CODE DATA ON SHEET LS-1. THE |
| DATA FOR THIS PROJECT SHOULD MATCH THE SHELL BUILDING |
| DATA. |
| A) AREA (TABLE 506.2) HAS UNLIMITED AREA FOR A BUSINESS |
| AND STORAGE OCCUPANCIES IN A FULLY SPRINKLERED BUILDING |
| OF TYPE 1B CONSTRUCTION. |
| B) FIRE-RESISTANCE RATING REQUIREMENTS (TABLE 601) ARE |
| FOR TYPE VB CONSTRUCTION AND THIS IS A 10 STORY |
| BUILDING OF TYPE 1B CONSTRUCTION. |
| |
| 4) FINISH PLAN NOTES #1 ON SHEET A2.1 STATES "REFER TO |
| SHEET A-1.5 FOR FINISH SPECIFICATIONS". THERE IS NO |
| SHEET A-1.5 IN THE SHEET INDEX OR ON THE PLANS. FBC |
| 107.2.1 |
| |
| 5) ACCESSIBLE SEATING IS REQUIRED AT THE FIXED CENTER |
| COUNTER AND THE FIXED BENCH SEATING AREA PER FBC |
| ACCESSIBILITY 902.1 AND 903.1. SEE SHEET A4.1. |
| |
| 6) THE RECEPTION SERVICE COUNTER IS REQUIRED TO COMPLY |
| WITH FBC ACCESSIBILITY 904.4 |
| |
| 7) SHOW THAT DOOR #125 TO THE WOMEN'S BATHROOM COMPLIES |
| WITH FBC ACCESSIBILITY 404.2.4.1 FOR MANEUVERING |
| CLEARANCES OR FRONT APPROACH ON THE PULL SIDE. |
| |
| 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |
| |
| |