2020-03-13 15:38:56RESIDENTIAL (R3) SHUTTERS THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MET WITH MR. ROTHMAN. I PRINTED THE FLORIDA PRODUCT
 APPROVAL HE SAID WAS THE CORRECT ONE (CLEAR PANEL) TO
 SEE IF THE PERMIT COULD BE APPROVED. AFTER REVIEWING
 THE SHUTTERS INSTALLATION SCHEDULE I NOTICED THAT THE
 OPENINGS DIMENSIONS WERE INCORRECT. ALSO, THE CLEAR
 PANEL SHUTTERS COULD NOT BE USED BASED ON THE SPECIFIED
 DESIGN PRESSURES AND SHUTTERS SPAN. WENT OVER THESE
 COMMENTS WITH MR ROTHMAN. I TOLD HIM THAT HE NEEDS TO
 COMPLETELY REVISE THE INSTALLATION SCHEDULE AND
 RE-SUBMIT FOR REVIEW.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER