Plan Review Notes For Permit 19090965 |
Permit Number |
19090965 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-04 10:59:35 | PERMIT # 19090965 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1. CLARIFICATION ON THE INSTALLATION ON THE SPECIFIC | | PIPE SIZE THE PLANS INDICATES 2 1/2 " BUT THE PERMIT | | APPLICATION INDICATES 3" | | 2. SUPPORTING DOCUMENTS TO SUPPORT THE WATER SUPPLY | | DEMANDS FOR THE DESIGNED UNDERGROUND PIPING SIZE | | 3. THE WORKING PLAN SUBMITTAL SHALL INCLUDE THE | | MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR ANY | | SPECIALLY LISTED EQUIPMENT, INCLUDING DESCRIPTIONS, | | APPLICATIONS, AND LIMITATIONS FOR ANY DEVICES, PIPING, | | OR FITTINGS. | | | | | | BRITTANY WOODS | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4754 | | | | |
|