2019-10-09 17:47:22 | ELECTRICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. AIC RATING OF SERVICE DISCONNECT AND PANEL |
| FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| NOT LESS THAN 10,000 AMPERES. (110.9) |
| |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| |
| 2. THE 3-2/0 SERVICE CONDUCTORS SUPPLYING TWO 150 AMP |
| PANEL IS UNDERSIZED. SERVICE CONDUCTORS SHALL BE SIZED |
| PER TABLE 310.15 (B) (16). |
| |
| 3. LOAD CALC'S FOR EACH PANEL IS INCOMPLETE. LOAD |
| CALC'S SHALL BE CALCULATED PER TABLE E3602.2 INCLUDE 3 |
| VA PER SQ/FT AND SEPERATE WASHER AND DRYER LOADS. |
| |
| 4. SPECIFY EQUIPMENT GROUNDING CONDUCTOR BETWEEN FEEDER |
| AND EACH PANEL PER E3704.6. |
| |
| 5. GROUNDING ELECTRODE SYSTEM SHALL BE PER E3608.4. |
| DEMONSTRATE ACCESS TO EXISTING WATER PIPE OR FOOTING |
| STEEL OR PROVIDE TWO GROUND RODS. |
| |
| 6. PROVIDE INTER SYSTEM BONDING CONNECTION PER E3609.3. |
| |
| 7. CEILING MOUNTED LUMINAIRE CLEARANCES IN CLOSETS |
| SHALL COMPLY WITH E4003.12. |
| |
| 8. OUTLETS SHALL BE PROVIDED AT FRONT AND REAR OF |
| STRUCTURE PER E3901.7. |
| |
| 9. PROVIDE SERVICE OUTLETS FOR A/C CU'S PER E3901.12. |
| |
| 10. EXISTING FIREPLACE REQUIRES CARBON MONOXIDE |
| DETECTORS PER R315.1. |
| |
| 11. OUTLETS REQUIRED NEXT TO BATHROOM BASINS PER |
| E3901.6. |
| |
| 12. CIRCUTS 18 & 20 AT 1ST PANEL INDICATES 14 AMP |
| BREAKERS. BREAKER SIZING SHALL BE PER E3705.6. |
| |
| 13. AFCI PROTECTION SHALL BE PER E3902.16. A NOTE ON |
| THE PLAN WILL SUFFUCE. |
| |
| 14. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF |
| THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |