Plan Review Notes
Plan Review Notes For Permit 19090939
Permit Number 19090939
Review Stop E
Sequence Number 1
Notes
Date Text
2019-10-09 17:47:22ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. THE 3-2/0 SERVICE CONDUCTORS SUPPLYING TWO 150 AMP
 PANEL IS UNDERSIZED. SERVICE CONDUCTORS SHALL BE SIZED
 PER TABLE 310.15 (B) (16).
  
 3. LOAD CALC'S FOR EACH PANEL IS INCOMPLETE. LOAD
 CALC'S SHALL BE CALCULATED PER TABLE E3602.2 INCLUDE 3
 VA PER SQ/FT AND SEPERATE WASHER AND DRYER LOADS.
  
 4. SPECIFY EQUIPMENT GROUNDING CONDUCTOR BETWEEN FEEDER
 AND EACH PANEL PER E3704.6.
  
 5. GROUNDING ELECTRODE SYSTEM SHALL BE PER E3608.4.
 DEMONSTRATE ACCESS TO EXISTING WATER PIPE OR FOOTING
 STEEL OR PROVIDE TWO GROUND RODS.
  
 6. PROVIDE INTER SYSTEM BONDING CONNECTION PER E3609.3.
  
 7. CEILING MOUNTED LUMINAIRE CLEARANCES IN CLOSETS
 SHALL COMPLY WITH E4003.12.
  
 8. OUTLETS SHALL BE PROVIDED AT FRONT AND REAR OF
 STRUCTURE PER E3901.7.
  
 9. PROVIDE SERVICE OUTLETS FOR A/C CU'S PER E3901.12.
  
 10. EXISTING FIREPLACE REQUIRES CARBON MONOXIDE
 DETECTORS PER R315.1.
  
 11. OUTLETS REQUIRED NEXT TO BATHROOM BASINS PER
 E3901.6.
  
 12. CIRCUTS 18 & 20 AT 1ST PANEL INDICATES 14 AMP
 BREAKERS. BREAKER SIZING SHALL BE PER E3705.6.
  
 13. AFCI PROTECTION SHALL BE PER E3902.16. A NOTE ON
 THE PLAN WILL SUFFUCE.
  
 14. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  