Plan Review Notes
Plan Review Notes For Permit 19090931
Permit Number 19090931
Review Stop M
Sequence Number 2
Notes
Date Text
2019-11-27 09:23:222ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19090931
 11/27/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #2 FROM THE 1ST REVIEW STILL EXIST- PLEASE
 COMPLY.
  
 2) REFER TO SECTION R403.7.1 FBC EC: THE SUBMITTED AC
 COOLING AND HEATING LOAD CALCULATIONS ARE INCOMPLETE.
 MISSING FROM THE PROJECT SUMMARY IS THE DIRECTIONAL
 ORIENTATION OF THE ADDITION AND THE COOLING AND HEATING
 EQUIPMENT SUMMARIES.
 PLEASE INDICATE IN THE NOTES ON THE FORM THAT THE
 CALCULATIONS ARE FOR THE NEW FAMILY ROOM ADDITION.
  
 1) NEW COMMENT SHEET M-1: PROVIDE A N AC EQUIPMENT
 SCHEDULE ON THE NEW MECHANICAL PLAN- SECTIPON 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  