Plan Review Notes
Plan Review Notes For Permit 19090931
Permit Number 19090931
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-15 13:34:26RESIDENTIAL (R3), ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- THIS PROPERTY IS LOCATED IN A AREA WITH QUESTIONABLE
 SOIL. PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC.
 R401.4 FBC-RESIDENTIAL.
 NOTE: ARCHITECT SPECIFY VIBRO-COMPACTION ON THE
 BUILDING AREA ON SHEET A-4 AND SHEET S-1.
 VIBRO-COMPACTION TO BE COORDINATED WITH THE
 GEOTECHNICAL REPORT RECOMMENDATIONS.
  
 2- PLANS NEED TO PROVIDE SPECIFICATIONS FOR THE VAPOR
 RETARDER AS REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
 NOTE: ALSO, PROVIDE SPECIFICATIONS SHOWING HOW THE
 VAPOR RETARDER WILL BE INSTALLED ON THE EXISTING
 CONCRETE SLAB THAT IS GOING TO RECEIVE THE NEW CONCRETE
 SLAB ON TOP.
  
 3- A) ROOF INSULATION SHOWN ON SECTION A-A ON SHEET S-1
 DOESN'T PROVIDE THE MIN. 1 INCH CLEARANCE REQUIRED BY
 SEC. R806.3 FBC-RESIDENTIAL FOR CROSS VENTILATION.
 REVISE AS REQUIRED TO COMPLY.
  
 B) ROOF VENT CALCULATIONS ARE REFERENCING THE 2014
 CODE. THE CURRENT CODE IS THE 2017 CODE, 6TH EDITION.
 REVISE AS REQUIRED.
 NOTE: THIS APPLIES TO THE "RENOVATION REQUIREMENTS" AND
 "GENERAL NOTES" ON SHEET A-1 ALSO. REVISE AS REQUIRED.
 CHAPTER 553 FLORIDA STATUTES
  
 4- PLANS ARE MISSING THE SPECIFICATIONS FOR BEAM #1 AND
 BEAM #2. PROVIDE COMPLETE DETAIL/SPECIFICATIONS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 5- FLASHING INFORMATION SHOWN ON SHEET A-5 CORRESPONDS
 TO WOOD FRAMED BUILDINGS. THIS DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. PROVIDE FLASHING INFORMATION FOR
 CONCRETE BLOCK CONSTRUCTION. SEC. R703.1
 FBC-RESIDENTIAL.
  
 6- ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS
 PROJECT, THE STRUCTURE IS LOCATED IN AN AE FLOOD ZONE
 WHICH IS A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD
 ELEVATION FOR THE PROPERTY IS 12.1' NAVD 88. THE CITY
 OF WEST PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT
 REQUIRES A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE
 LOWEST FLOOR AND ALL EQUIPMENT SERVICING THE RESIDENCE
 IS REQUIRED TO BE AT OR ABOVE 14.1' NAVD 88.
 BASED ON THE PROPERTY APPRAISER THE ADDITION IS
 CONSIDERED A SUBSTANTIAL IMPROVEMENT.
 THE ADDITION AND THE EXISTING HOUSE NEED TO COMPLY WITH
 THE FLOOD REQUIREMENTS.
  
 BASED ON THE SURVEY SUBMITTED, IT LOOKS LIKE THE
 FINISHED FLOOR OF THE EXISTING HOUSE MAY BE COMPLAINT
 WITH THE MIN. FINISHED FLOOR ELEVATION REQUIRED BY THE
 CITY FLOOD ORDINANCE (2 FEET ABOVE BASE FLOOD
 ELEVATION).
 BUT, SURVEY NEEDS TO BE REVISED. SURVEY IS MISMATCHING
 TWO DIFFERENT ELEVATION REFERENCES. THE INFORMATION
 UNDER THE LEGAL DESCRIPTION IS PROVIDING THE BASE FLOOD
 ELEVATION USING THE NAVD 88 REFERENCE, WHILE THE
 FINISHED FLOOR ELEVATION OF THE HOUSE IS IS USING NGVD
 29. REVISE SURVEY AS REQUIRED USING THE CURRENT
 REFERENCE NAVD 88.
  
 SINCE THIS PROPERTY IS LOCATED IN FLOOD ZONE AE, THEN
 ELEVATION CERTIFICATES ARE REQUIRED FOR BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION. SEC. 18-284
 CITY ORDINANCE NO. 4729-17. NOTE: THIS WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY FORM SUBMITTED R405-2014 IS FOR THE 2014
 CODE. THE CURRENT CODE IS THE 2017 6TH EDITION FBC.
 REVISE AS REQUIRED. PROVIDE CALCULATIONS USING THE
 CURRENT FORM.
 SEC. 1101.1 FBC-EXISTING BUILDING AND SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 B) THE ENERGY FORM IS REQUIRED TO BE CERTIFIED AT THE
 BOTTOM BY THE OWNER OR THE OWNER LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) CEILING INSULATION SPECIFIED ON ITEM #10 DOESN'T
 MATCH ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 SEE PLANS
 AND REVISE AS REQUIRED.
  
 D) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION
  
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 F)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4
 DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. REVISE
 AS REQUIRED. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 G) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2.
  
 H) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 8- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)PRECAST LINTEL AS SPECIFIED ON PLANS. NOA 14-0903.03
 SUBMITTED IS FOR 4", 6" & 12" PRECAST LINTELS.
 ARCHITECT SPECIFIED 8" PRECAST LINTELS. ALSO, NOA
 SUBMITTED IS EXPIRED.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  