Plan Review Notes
Plan Review Notes For Permit 19090882
Permit Number 19090882
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-14 08:34:001ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE FOLLOWING REQUIRED ACCESSIBILITY
 DETAILS PER WPB AMEND TO FBC 107.2.1
  
 A)ON ALL ENLARGED BATHROOM DETAILS LABEL CLEAR FLOOR
 SPACES FOR FBC ACC 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES \
 MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 B)ON ALL ENLARGED BATHROOM DETAILS AND BREAK ROOM SINK
 LABEL CLEAR FLOOR SPACES AND SHALL BE CENTERED FOR
 LAVATORY'S AND SINKS, FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED. EXCEPTIONS: 1.A
 PARALLEL APPROACH COMPLYING WITH 305 SHALL BE PERMITTED
 TO A KITCHEN SINK, IN A SPACE WHERE A COOK TOP OR
 CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET BARS.
  
 C)FBC ACC 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET
 ABOVE THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND
 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT.
 SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION.
  
 D)FBC ACC 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR
 SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL.
  
 E)FBC ACC 604.5.2 REAR WALL.THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE.
  
 F)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 G)FBC ACC 604.7 DISPENSERS.TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]