2019-11-06 15:17:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090882
 11/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-301 & M-501: IT APPEARS AHU & CU 1-7 HAVE
 BEEN MISLABELED AS AHU & CU 1-2 ON THE FLOOR PLAN
 LAYOUT- PLEASE CORRECT.
  
 2) M-501: PROVIDE O/A CALCULATIONS FOR THE NEW RETAIL
 AC SYSTEM- TABLE 403.3.1.1 FBC M.
  
 3) M-310: VERIFY THE RETAIL O/A INTAKE LOCATION IS IN
 COMPLIANCE WITH SECTION 401.4 FBC M FOR REQUIRED
 CLEARANCES.
  
 4) M-303: A FIRE/SMOKE DAMPER IS REQUIRED AT THE
 PENETRATION OF THE 12X12 OA DUCT INTO THE SHAFT PER
 607.5.5 FBC M.
  
 5) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE FIRE DAMPERS AND
 FIRE/SMOKE DAMPERS (IF REQUIRED). THE SPECS MAY BE
 DEFERRED SUBMITTALS PER SECTION 107.3.4.1 WPB.
  
 6) M-301: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 NEW RETAIL AHU- SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  