2019-11-06 15:17:15 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19090882 |
| 11/5/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M-301 & M-501: IT APPEARS AHU & CU 1-7 HAVE |
| BEEN MISLABELED AS AHU & CU 1-2 ON THE FLOOR PLAN |
| LAYOUT- PLEASE CORRECT. |
| |
| 2) M-501: PROVIDE O/A CALCULATIONS FOR THE NEW RETAIL |
| AC SYSTEM- TABLE 403.3.1.1 FBC M. |
| |
| 3) M-310: VERIFY THE RETAIL O/A INTAKE LOCATION IS IN |
| COMPLIANCE WITH SECTION 401.4 FBC M FOR REQUIRED |
| CLEARANCES. |
| |
| 4) M-303: A FIRE/SMOKE DAMPER IS REQUIRED AT THE |
| PENETRATION OF THE 12X12 OA DUCT INTO THE SHAFT PER |
| 607.5.5 FBC M. |
| |
| 5) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE FIRE DAMPERS AND |
| FIRE/SMOKE DAMPERS (IF REQUIRED). THE SPECS MAY BE |
| DEFERRED SUBMITTALS PER SECTION 107.3.4.1 WPB. |
| |
| 6) M-301: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| NEW RETAIL AHU- SECTION 307.2.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |