2019-11-18 15:29:47 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19090882 |
| REVIEWED: NOVEMBER 18, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 404.6 FBC[B]ENCLOSURE OF ATRIUMS. ATRIUM SPACES |
| SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR |
| FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 707 |
| OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 711, OR BOTH. |
| HOW ARE BOTH LEVELS OF ATRIUM SEPARATED FROM ADJACENT |
| SPACES? THE LIFE SAFETY PLAN SHOW A DASH DOT LINE ON |
| THE FIRST FLOOR THAT MAY REPRESENT 1 HOUR RATING, BUT |
| IT IS NOT DENOTED WHAT THE LINE REPRESENTS. |
| ALSO, IT WAS DISCUSSED IN A MEETING ABOUT FIRE CURTAINS |
| AT THE 2 ND FLOOR OPENINGS. |
| HOW IS THE SECOND LEVEL SEPARATED AS REQUIRED IN 404.6? |
| |
| 2) 716.5 FBC TABLE[B]OPENING FIRE PROTECTION |
| ASSEMBLIES, RATINGS AND MARKINGS. |
| PLEASE LIST FIRE RATING OF ALL EXISTING DOORS IN RATED |
| WALLS AND SHAFTS. |
| ALSO, PROVIDE SPECIFICATIONS FOR ANY FIRE CURTAINS |
| BEING INSTALLED, OR INDICATE THAT THEY WILL BE A |
| DEFERRED SUBMITTAL. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |