2019-11-18 15:29:47BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19090882
 REVIEWED: NOVEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 404.6 FBC[B]ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 707
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 HOW ARE BOTH LEVELS OF ATRIUM SEPARATED FROM ADJACENT
 SPACES? THE LIFE SAFETY PLAN SHOW A DASH DOT LINE ON
 THE FIRST FLOOR THAT MAY REPRESENT 1 HOUR RATING, BUT
 IT IS NOT DENOTED WHAT THE LINE REPRESENTS.
 ALSO, IT WAS DISCUSSED IN A MEETING ABOUT FIRE CURTAINS
 AT THE 2 ND FLOOR OPENINGS.
 HOW IS THE SECOND LEVEL SEPARATED AS REQUIRED IN 404.6?
  
 2) 716.5 FBC TABLE[B]OPENING FIRE PROTECTION
 ASSEMBLIES, RATINGS AND MARKINGS.
 PLEASE LIST FIRE RATING OF ALL EXISTING DOORS IN RATED
 WALLS AND SHAFTS.
 ALSO, PROVIDE SPECIFICATIONS FOR ANY FIRE CURTAINS
 BEING INSTALLED, OR INDICATE THAT THEY WILL BE A
 DEFERRED SUBMITTAL.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  