Plan Review Notes
Plan Review Notes For Permit 19090859
Permit Number 19090859
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-29 07:41:40JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?SHUTTER GLASS SEPARATION?; PROVIDE INFORMATION
 FROM SHEET 11 FL1850. COLUMN HEADING ?SHUTTER SPAN?;
 PROVIDE INFORMATION FROM SHEET 5 FL1850, THE TOP OF THE
 SHUTTER BLADE TO THE BOTTOM OF THE SHUTTER BLADES
 LENGTH. COLUMN HEADING ?MINIMUM EDGE DISTANCE?; PROVIDE
 INFORMATION FROM SHEET 16 & 17 FL1850. COLUMN HEADING
 ?ANCHOR SPACING? PROVIDE INFORMATION FROM SHEET 15
 FL1850. EXAMPLE SUBSTRATE SOUTHERN PINE, MAXIMUM SPAN
 7?-0? A.S.D DESIGN NEGATIVE PRESSURE RATING (PSF) 60
 WALL MOUNTINGS P & Q ANCHOR SPACING IS 4? MAXIMUM.
 SECOND REQUEST
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved