Plan Review Notes For Permit 19090816 |
Permit Number |
19090816 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-11-05 15:29:38 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PANEL SCHEDULE SHOWS 3 MOTORS I DO NOT SEE THREE | | MOTORS PLEASE INDICATE WHERE THESE MOTORS ARE LOCATED. | | HOW FAR FROM THE PANEL ARE THESE MOTORS (GATE OPENERS) | | LOCATED | | | | 2) VALUE IS TO INCLUDE THE VALUE OF THREE GATE OPENERS | | IF THERE IS THREE OR HOW EVER MANY ARE BEING INSTALLED. | | SHOW BREQAK DOWN OF VALUE FOR LABOR AND EQUIPMENT | | GATE OPENERS WERE DESIGNATED AS FUTURE ON ORIGINAL | | PERMIT . |
|